Connecting The Electrical Wiring; Specifications Of Standard Wiring Components; To Connect The Electrical Wiring On The Indoor Unit - Daikin FBA35A2VEB Manual De Instalación

Ocultar thumbs Ver también para FBA35A2VEB:
Tabla de contenido

Publicidad

2 Check for leaks by applying the bubble test solution to all
connections.
3 Discharge all nitrogen gas.
5.3

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
5.3.1
Specifications of standard wiring
components
Component
(a)
Power supply
MCA
cable
Voltage
Phase
Frequency
Wire sizes
Interconnection cable
User interface cable
Recommended field fuse
Earth leakage circuit breaker
(a)
MCA=Minimum circuit ampacity. Stated values are
maximum values (see electrical data of combination with
indoor units for exact values).
5.3.2
To connect the electrical wiring on the
indoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located on the switch box cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
It is important to keep the power supply and the transmission wiring
separated from each other. In order to avoid any electrical
interference the distance between both wirings should ALWAYS be
at least 50 mm.
NOTICE
Be sure to keep the power line and transmission line apart
from each other. Transmission wiring and power supply
wiring may cross, but may NOT run parallel.
1 Remove the service cover.
2 User interface cable: Route the cable through the frame,
connect the cable to the terminal block, and fix the cable with a
cable tie.
(2)
Dashed line represents separate power supply.
FBA35~140A2VEB9+FBA35~71A2VEB9+ADEA35~125A2VEB
Split system air conditioners
4P456962-1D – 2018.08
Class
35+50 60+71
100
125+140
1.4 A
1.3 A
3.5 A
3.9 A
220~240 V
1~
50/60 Hz
Must comply with applicable
legislation
Minimum cable section of
2.5 mm² and applicable for
220~240 V
Vinyl cord with 0.75 to 1.25 mm
sheath or cables (2 core wires)
Maximum 500 m
16 A
Must comply with applicable
legislation
3 Interconnection cable (indoor↔outdoor): Route the cable
through the frame, connect the cable to the terminal block
(make sure the numbers match with the numbers on the
outdoor unit, and connect the earth wire), and fix the cable with
a cable tie.
4 Divide the small sealing (accessory) and wrap it around the
cables to prevent water from entering the unit. Seal all gaps to
prevent small animals from entering the system.
WARNING
Provide adequate measures to prevent that the unit can be
used as a shelter by small animals. Small animals that
make contact with electrical parts can cause malfunctions,
smoke or fire.
5 Reattach the service cover.
▪ When using 1 user interface with 1 indoor unit.
a
b
c
1 2 3
L N
1 2 3
L N
P
P
1
2
2
P
P
1
2
d
▪ When using 2 user interfaces
a
b
b
c
c
1 2 3
L N
1 2 3
P
P
1
2
P
P
P
P
1
2
1
2
d
d
▪ When using group control
5 Installation
a
a
b
b
c
c
1 2
3
L N
1 2 3
L N
P
P
1
2
P
P
1
2
d
2
a
L N
2
Installation manual
11

Publicidad

Tabla de contenido
loading

Tabla de contenido