3. Connection to network
To connect the G10-LON interface to the network, remove the front cover
and activate the Service PIN button. When the button is activated, the
G10-LON interface transmits a unique 48 bit ID-code (Neuron ID), which is
registered by the network.
This unique code can also be found on the label situated on the side of the
G10-LON interface. The bar code is in Code 128 format.
An additional label with the same unique code is supplied with the G10-LON
interface. This label can be attached to the building installation plan.
4. Technical data
Pump to G10
Transceiver type
RS-485
Screened twisted-pair cable.
Recommended cable
Cross section: 0.25 - 1 mm².
Max. cable length: 1200 m.
Transmission speed
9.6 kBits/s
Protocol
GENIbus
Supply voltage
External 24 VAC/VDC ±25%
Current consumption
Ca. 100 mA
Enclosure class
IP 42
Cable entries
3 x Pg 7
4.1 Temperature conditions
Ambient temperature: 0°C to +60°C.
Storage temperature: –30°C to +70°C.
4.2 Service LED
The Service LED on the front plate of the G10-LON interface is a light-emit-
ting diode indicating various conditions of the LON network.
For further information, see the documentation files on the floppy disk sup-
plied with the G10-LON interface.
8
G10 to LON
FTT - 10
Unscreened twisted-
pair cable
78 kBits/s
LonTalk