Adjusting setpoint
Put the cursor (=>) in front of the "CO2 set" line by
rotating the PTB, and then push the PTB.
A blinking square will appear in front of the CO2
set value. By rotating the PTB, you can set the
desired CO2 concentration. Confi rm this value by
pushing the PTB or wait a few seconds for
automatic confi rmation.
=> CO2 set
700 ppm
CO2 +/-
50 ppm
>> NEXT >>
Adjusting hysteresis (BANDWITH)
Put the cursor (=>) in front of the "CO2 +/-" line by
rotating the PTB, and then push the PTB.
A blinking square will appear in front of the CO2
+/- value. By rotating the PTB, you can set the
desired CO2 hysteresis (recommended: 50 ppm).
Confi rm this value by pushing the PTB or wait a
few seconds for automatic confi rmation.
CO2 set
700 ppm
=> CO2 +/-
50 ppm
>> NEXT >>
By selecting the line ">> NEXT >>" and press the
DDK, you will reach the "CO2 counter" menu.
Today dose 16m15s
Total
14h36m
Reset total
=>
>> NEXT >>
If you click on the >> NEXT >> button, you will see
the following screen.
CO2 Min
557ppm
CO2 Max
1027ppm
Reset min/max
=> >> NEXT >>
By pressing "reset min / max" the minimum and
maximum values of CO2 will be reset.
CO2 counter
The T-1 controller keeps track of the CO2 dosing.
The daily dosing time and the total dosing time.
The "Today" will be reset at the beginning of each
cycle. (3 sec after the detection of light)
Total dose is an enumeration of the total dosing
times of the controller.
TMP = 25.5 C
RH
= 32 %
=> CO2 = 539 ppm
CO2 set
700 ppm
CO2 +/-
50 ppm
=> >> NEXT >>
Today dose 16m15s
Total
1h03m
=> Reset total
>> NEXT >>
Place the cursor at "total reset" and press the
DDK to reset the "CO2 counter".