Introduction
Note the following dependencies for PROFINET IO during configuration of ET 200SP fail-safe modules per with GSD file.
Note
When using ET 200SP fail-safe modules with the GSD file on external masters, note that the warnings, information and
references contained in the F-module device manuals are still valid for other manuals.
Please also observe the external master specifications.
Requirement
ET 200SP fail-safe modules can be used with the GSD file on the following interface modules:
IM 155-6 PN ST as of V3.1 (as of V4.1 for F-DI 8x24VDC HF 6ES7136-6BA01-0CA0)
IM 155-6 PN HF as of V3.1 (as of V4.2 for F-DI 8x24VDC HF 6ES7136-6BA01-0CA0)
IM 155-6 PN/2 HF as of V4.2
IM 155-6 PN/3 HF as of V4.2
IM 155-6 PN HS as of V4.0
IM 155-6 MF HF as of V5.0
An S7-FCT is required to calculate the F_iParCRC and address the F-I/O.
Note
If the identification during the assignment of the PROFIsafe address does not succeed, e.g. the F module flashes
continuously, the following corrective measures are possible:
Pull/plug the F module.
Repeat the assignment of the PROFIsafe address after approx. 2 minutes.
Increase the PROFINET update time of F host and IM for the duration of the F address assignment.
S7-FCT allows you to configure selected F-I/Os from SIEMENS in an engineering system from another manufacturer.
You can find S7-FCT on the Internet (https://support.industry.siemens.com/cs/ww/en/view/109762827).
Observe the minimum requirements for the installation of the F-system to be used.
Table 1
Configuration software and requirements
Configuration software
STEP 7 (TIA Portal) as of V15
STEP 7 as of V5.5 SP4 HF19
STEP 7 as of V5.6 HF5 or higher
STEP 7 as of V5.6 SP1 HF5
Software of another manufacturer
We recommend that you use the latest HF.
Note
Observe the module-specific restrictions.
Dependencies F-DQ 4x24VDC/2A PM HF (6ES7136-6DB00-0CA0) as
of firmware version V2.0.0
Reintegration after a channel fault depends on the F-host used. You can find information on this in the documentation of the
F-host. The F module supports configuration per GSD file PROFIsafe V2.4.
When configuring with GSD file, only module-wide passivation is possible.
In TIA Portal, the "IO Tags" tab displays more tags than supported by the F module.
Dependencies during configuration with GSD files for ET 200SP fail-safe modules
A5E32311847-AC, 09/2021
Requirements
S7-FCT V2.0
Information on installation
STEP 7 online help
Documentation of the manufacturer
7