25112
Thermostat operation
1 - Description
3
1
2
1 LED indicating output state
ON = request for heating
2 Temperature setting knob
3 to select the value of the 'reduced' setting
4 Potentiometer for thermostat calibration
5 Switch ON/OFF of the LED
2 - Lowering input
Your thermostat is fitted an input for set point
reduction that lowers automatically the desired
temperature.
• No signal on input = the thermostat operates
according to the temperature setting.
• 230V signal on input = the thermostat uses
a «reduced» setting corresponding to the
temperature set at –3,5 °C.
3 - Locking of controls
You may limit the temperature adjustment range
by using a mechanical blocking (for instance
+/- 1 °C).
• Remove the setting knob.
• Remove the small pins from their support.
• Place them so as to define the temperature range
as desired.
• Reset the adjustment button on the cursor of
centre section and press gently.
Example: adjustment limited
to +/- 1 °C.
2
Thermostat d'ambiance électronique
a
Electronic room thermostat
z
Raumtemperaturthermostat
e
Termostato ambiental electrónico
r
Adjustments/settings
The settings below are to be done on back of
thermostat. To have access to the back, pull up
thermostat front face and remove it from its base.
a) Installation type
The switch 3 allows to select the value of the
4
'reduced' setting.
1 = lowering by 2 °C (suitable for installations with
5
high inertia, e.g. heating floor).
2 = lowering by 3,5 °C (suitable for installations
with no inertia).
b) Setting the temperature set point
The temperature may be set between 13°C and
27°C Marks 1 to 6 refer to the following settings: 1
= 13 °C, 2 = 16 °C, 3 = 19 °C, 4 = 21 °C, 5 = 24 °C
and 6 = 27 °C.
c) activating/deactivating operating led
Use
the
switch
thermostat D.
ON = led is active
OFF = led inactive. It only switches on temporarily
after acting upon the setting knob when request
is under way.
«1st Temperature Rise» Mode
This feature allows you to raise the temperature
of your heating floor gradually to limit the thermal
stress of the slab in the cold season and prevent
damage to your installation (cracks in slab...).
• To set the device ino this mode, clip
product
mounting
temperature button immediately (within 5
seconds) 3 times back-and-forth and from
-3 °C to +3 °C until the red LED flickers.
• The red thermostat LED will flicker On and Off in
a non-regular manner for 7 days, indicating that
the device is set into «1st Temperature Rise».
• After 7 days, the thermostat will exit automatically
pins
the «1st Temperature Rise» mode and control
temperature normally. If the thermostat is
powered off during this time (e.g. due to mains
power failure), the "1st Temperature Rise»
program will resume from the point it had
stopped when the power is restored (please do
not change the thermostat setting).
Note: it is not possible to stop the «1st Temperature
Rise» cycle, once it is started.
Where and how to install your
electronic thermostat?
The room thermostat must be installed at
approximately 1,5 m. up from floor upon an
interior wall, away from direct solar radiation and
any heat source such as television, lighting and
air draught etc.
The thermostat is made of two parts:
• a plug-in front face (b).
• a base to be fitted inside a Ø 60 mm flush-
mounted box (a).
to
activate/deactivate
5
front
face
on
the
flush-
section,
then
operate
the
This electronic room thermostat is especially
designed for commercial premises and offices.
The room temperature can be set at the back of
the device within +/- 3 °C limits.
Its input for set point reduction allows to connect
it to a time switch to provide additional savings,
for instance by automatically lowering room
temperature at night.
a) fix the base of your thermostat in a Ø 60 mm flush-
mounted box using 2 screws.
b) the front face
is just clipped
onto the
flush-mounted
assembly.
b
Note: to prevent parasitic air draughts, it is
recommended to block the electrical supply cable
with an insulating material (glass wool etc.).
Technical characteristics
Power supply:
230V+10/-15%, 50Hz
Output:
phase cut-off 10A – 230V AC1. max.
10A – 230V AC1. max.
100mA – 48V DC min.
Consumption:
Comfort temperature setting range:
Accuracy:
Drift under load:
Type of regulation:
Connection capacity:
Hygrometry:
Index of protection:
Class of insulation:
Ecodesign class:
Operating temperature:
Storage temperature:
Dimensions of the thermostat
(font part):
Made in France
Usable everywhere in Europe and Switzerland
Correct Disposal of This product
(Waste Electrical & Electronic
Equipment).
(Applicable in the European Union
and other European countries
with separate collection systmes).
This marking shown on the product or its literature
indicates that it should not be disposed with other
household wasted at the end of its working life. To
prevent possible harm to the environment or human
health from uncontrolled waste disposal, please
separate this from other types of wastes and recycle it
responsibly to promote the sustainable reuse of material
resources.
Household users should contact either the retailer
where they purchased this product, or their local
government office, for details of where and how they
can take this item for environmentally safe recycling.
Business users should contact their supplier and
check the terms and conditions of the purchase
contract. This product should not be mixed with other
commercial wastes of disposal.
a
< 0,5W
10 to 30 °C
< 0,5K
< 1,5K
PI
2
2 x 1 to 2,5 mm
90% to 25 °C
IP30/IK03
II
4
0 °C to +45 °C
-20 °C to +65 °C
85x81x13 mm
M
6LE000581B