parameter
p01
Temperature displayed on the LCD
p02
oFF mode LCD indications
p03
Room temperature correction
p04
Winter lower set-point limit
p05
Winter upper set-point limit
p06
Summer lower set-point limit
p07
Summer upper set-point limit
p08
Thermal differential for regulation
p09
Temperature display scale
p10
Winter / Summer selection
p11
Back-light timeout
p12
Auxiliary input functionality
p13
Restoring default parameters
End
Exit from the menu
(*) ± 0.3°C value is suitable for rooms with high thermal inertia, ± 2°C value is suitable for rooms with low thermal inertia.
(#) if option 5 is selected, the WInTER/SUmmER selection in P10 will be disabled.
Factory setup
value
1
1 = Room temperature / 2 = set-point temperature
1
1 = oFF message / 2 = Room temperature
0.0°C
± 4.0°C by steps of 0.1
2.0°C
2.0 ÷ 40.0 °C by steps of 0.1
40.0°C
40.0 ÷ 2.0 °C by steps of 0.1
2.0°C.
2.0 ÷ 40.0 °C by steps of 0.1
40.0°C.
40.0 ÷ 2.0 °C by steps of 0.1
0.3°C.
±0.3 ÷ 2.0 °C by steps of 0.1 (*)
CEL
CEL = Celsius / FAH = Fahrenheit
Wn
Wn = Winter / Su = Summer
05 s.
oFF = always off / 05÷30 = time delay (seconds)
1
1 = noT ConnECTED
2 = on/oFF InPUT: closed is oFF
3 = WInDoW ConTACT: open for Economy mode
4 = REDUCTIon: if closed the set-point will be
reduced by 3°C.
5 = REmoTE CHAnGE-oVER: closed=SUm,
open=WIn (#)
no
no = no editing of set parameters
YEs = restoring default settings
-
Confirming the choice exits the advanced setup
menu.