FlameGuard
Bushing with Metal Thread Insert
Installation Instructions
FG-3C-0805
Spears
®
bushing with
Metal Thread Insert is
designed to convert any
FlameGuard™
¿ tting socket to a 1/2"
threaded sprinkler head
¿ tting. This adapter can
be easily solvent cemented into Tees, Elbows,
couplings, etc. for direct connection of sprinkler
head. Threaded poly nipple is included to hold
adapter during installation and keep cement
out of threads.
System design and installation must be
made in accordance with criteria speci¿ ed in
Spears
®
publication, FG-3, FlameGuard™
CPVC Fire Sprinkler Products Installation
Instructions.
BASIC ADAPTER INSTALLATION
STEP 1
Thread Poly Nipple holding tool into Bushing.
1
STEP 2
Apply cement to fitting socket and Bushing
spigot end.
1"
STEP 3
Immediately insert Bushing into socket using a
1/4-turn.
Hold for 30 Seconds
45
45
2
STEP 4
Sprinkler head may be installed once the joint
has cured a minimum of 30 minutes.
System may be pressure tested
following speciÀ ed cure time schedule.
STEP 5
Apply thread sealant to sprinkler head male
threads.
THREADED CONNECTIONS SEALANTS
RECOMMENDED SEALANT:
®
Spears
Manufacturing Company highly recommends the
BLUE 75™ thread sealant, which has
®
use of Spears
been tested for compatibility with Spears
®
products. Please
follow the sealant Manufacturers' Application/Installation
instructions. Choice of another appropriate thread sealant
is at the discretion of the installer.
3
IF YOU MUST USE A TAPE SEALANT:
1. Use TFE tape no less than 2.5 mil thick.
2. Initial wrap must fully cover the thread end.
3. Wrap clockwise with standard pipe threads.
4. Use only 2-3 wraps of tape.
STEP 6
Apply wrench make-up of no more than one
to two turns beyond finger tight thread engagement. Care
must be taken in final positioning so as to avoid the need to
"back-out" (unthread) the wrenched assembly.
DO NOT OVER TIGHTEN AS DAMAGE MAY OCCUR.
NOT FOR USE WITH
COMPRESSED AIR OR GAS
SPEARS
®
MANUFACTURING COMPANY
CORPORATE OFFICE
15853 Olden Street, Sylmar, CA 91342
PO Box 9203, Sylmar, CA 91392
(818) 364-1611 • www.spearsmfg.com
© Copyright 2006 Spears
®
Manufacturing Company. All Rights Reserved.
Printed in the United States of America 03/06.
FG-3C-0805

Publicidad

loading

Resumen de contenidos para Spears FlameGuard

  • Página 1 ® use of Spears Spears ® publication, FG-3, FlameGuard™ been tested for compatibility with Spears ® products. Please follow the sealant Manufacturers’ Application/Installation CPVC Fire Sprinkler Products Installation instructions. Choice of another appropriate thread sealant Instructions.
  • Página 2 Spears ® Manufacturing Company recomienda altamente utilizar el sellante de rosca BLUE 75™ de Spears ® , que contaminamiento de solvente en la rosca. ha estado probado para la compatibilidad con los productos ®...

Este manual también es adecuado para:

Fg-3c-0805