The K550M panel features an electronic photocell control system which switches the photocell
transmitter on and off thereby causing the control unit microprocessor to check whether the
receiver r lay switches correctly.
If this does not happen, the control unit is automatically blocked.
ELECTRONIC CONTROL OF PHOTOCELL SAFETY DEVICES
•
MICROPROCESSOR-CONTROLLED LOGIC
•
INPUT STATUS LED'S
•
LINE INPUT FUSE
•
"PEDESTRIAN ACCESS" FUNCTION
•
BUILT-IN FLASHING LIGHT CIRCUIT
•
OP/CL TIMER SETTINGS
•
BUILT-IN 433.92 MHz SELF-LEARNING RECEIVER
•
RECEIVER CONNECTOR
•
1 –2 –3 POWER input 115 VAC 60 Hz 2=EARTH
4 –5 FLASHING LIGHT output 115 VAC 5 W max. The signal is already modulated for direct use. Flashing
frequency increases slightly during closing.
6 –7 –8 MOTOR output single-phase 115 VAC common=8; opening=6; closing=7; connect the capacitor
between terminals 6 and 7.
9 –12 OPEN/CLOSE pushbutton input (Normally Open contact);
refer to functions of dip switches N°4 and N°2 (12=Common).
10 –12 PEDESTRIAN pushbutton input (Normally Open contact);
similar to the OPEN/CLOSE pushbutton but only travels about 1 m;used to control pedestrian traffic
(12=Common).
11 –12 STOP pushbutton input (Normally Closed contact); Stops the gate. (12=Common).
13 –14 OPEN LIMIT SWITCH input (Normally Closed contact); 13=Common.
13 –15 CLOSE LIMIT SWITCH input (Normally Closed contact); 13=Common.
13 –16 FIXED SAFETY EDGE input (Normally Closed contact);
Works only when the gate is opening; temporarily stops the gate and partially closes it by about 20 cm in
order to allow the obstacle to be removed. (13=Common).
13 –17 PHOTOCELL OR SAFETY DEVICES input (Normally Closed contact);
They stop the gate during closing and totally reopen it; they temporarily stop the gate during opening in
order to allow the obstacle to be removed (if dip switch N°3 set to ON), (13=Common).
N.B.: the photocell transmitter must always be connected (terminals 26-27) as it is checked by the
safety system; the control unit will not work if it is disconnected. To disable the safety system
move dip switch N°6 to OFF.
18 –19 built-in RX aerial input; 18=EARTH 19=SIGNAL
20 –21 2nd RADIO CHANNEL output used with auxiliary two-channel receiver for opening/closing another
gate or controlling garden illumination.
22 –23 push-in RX AERIAL 22=SIGNAL 23=GROUND
24 –25 GATE OPEN LED output 24 VAC 3 W; the LED flashes slowly during opening, remains on when
the gate is open and flashes rapidly during closing.
26 –27 24 VAC 1 W POWER output for PHOTOCELL TX .
28 –29 24 VAC 1 W POWER output for PHOTOCELL RX, EXTERNAL RECEIVERS, etc.
English
TERMINAL BOARD CONNECTIONS
Pag. 3