Start-up
5.1 Setting outlet pressure
Set outlet pressure min. 1 bar under inlet pressure.
1.
Close shut-off valve on inlet
2.
Release pressure on outlet side (e.g. through water
tap)
3.
Fit pressure gauge (optional)
4.
Close shut-off valve on outlet
5.
Loosen slotted screw
• Do not remove slotted screw
6.
Slacken tension in compression spring
• Turn adjustment handle counter clockwise (-) until
it does not move any more
7.
Slowly open shut-off valve on inlet
8.
Turn adjuster knob until the manometer shows the
desired value
9.
Re-tighten slotted screw
10.
Slowly open shut-off valve on outlet
6
Maintenance
In order to comply with EN 806-5, water fixtures must
be inspected and serviced on an annual basis.
As all maintenance work must be carried out by an
installation company, it is recommended that a
servicing contract should be taken out.
CAUTION!
Risk of burns due to hot water and hot surfaces.
Wear safety gloves!
In accordance with EN 806-5, the following measures must
be taken:
6.1 Inspection
1.
Close shut-off valve on outlet
2.
Check outlet pressure using a pressure meter when
there is zero through-flow
• If the pressure is increasing slowly, the valve may
be dirty or defective. In this instance, carry out
servicing and cleaning (See 6.2 Maintenance)
3.
Slowly open shut-off valve on outlet
MU0H-1043 GE23 R1119
GB
6.2 Maintenance
Do not use any cleansers that contain solvents and/or
alcohol for cleaning the plastic parts, because this can
cause damage to the plastic components - water
damage could result.
Detergents must not be allowed to enter the
environment or the sewerage system!
1.
Close shut-off valve on inlet
2.
Release pressure on outlet side (e.g. through water
tap)
3.
Close shut-off valve on outlet
4.
Loosen slotted screw
• Do not remove slotted screw
CAUTION!
There is a spring in the spring bonnet. It may cause
injuries if the spring is derailing.
• Make sure tension in compression spring is
slackened!
5.
Slacken tension in compression spring
• Turn adjustment handle counter clockwise (-) until
it does not move any more
6.
Unscrew spring bonnet
• Use double ring wrench ZR06K
7.
Remove slip ring
8.
Remove valve insert with a pair of pliers
9.
Remove filter, clean and reinsert
10.
Check that sealing ring, edge of nozzle and slotted
ring are in good condition, and if necessary replace
the entire valve insert
11.
Reassemble in reverse order
CAUTION!
Press in diaphragm with finger before inserting slip
ring
12.
Adjust setting scale and set outlet pressure
3