Installation
S19345HXB, S19345HXBT, S19345HFB, S19345HFBT, S19345JXB, S19345JXBT, S19345JFB, S19345JFBT

Safety Information

To ensure proper operation:
Installation
This fixture has been designed and 3rd party tested to meet ANSI/ISEA Z358 .1 . The system must be tested
periodically to be sure it is functioning properly to meet the standard . Please refer to the ANSI/ISEA Z358 .1
standard on testing requirements .
The installation, maintenance and location of all safety drench showers, eye and eye/face washes must comply
with the requirements of ANSI/ISEA Z358 .1 . Workers who may come in contact with potentially hazardous
materials should be trained regarding the location and proper operation of emergency equipment per ANSI/
ISEA Z358 .1 .
ANSI/ISEA Z358 .1 requires this unit to be used with a clean, potable, uninterrupted supply of tepid water .
Bradley plumbed emergency fixtures require a minimum of 30 psi flowing pressure in order to function as
designed and meet the ANSI/ISEA Z358 .1 standard .
Before installation make sure that this equipment will meet the requirements of the potential hazardous
contaminants in your location .
Installation of this system must be completed by a qualified plumber in compliance with all national and
local codes . Compliance and conformity to drain requirements and other local codes and ordinances is the
responsibility of the installer .
Weekly Inspections
To ensure all emergency shower and eye/face wash fixtures are ready to be used when needed, regular
checks and maintenance must be conducted . Weekly inspections must be conducted on all safety equipment
to make sure a suitable flushing fluid supply is present and to make sure the equipment is in good operating
condition .

Water Temperature

ANSI/ISEA Z358 .1 requires tepid water . Suitable range is 60°F to 100°F (16°C to 38°C) . Personal injury is
possible outside this temperature range .

Supplies Required

• Ø 1" (25mm) nominal copper tubing
for supply line on unit
• Bolts for cabinet mounting
• Teflon tape and pipe sealant
• Sign-mounting hardware
• Piping 1" NPT between valve and
showerhead
Bradley • 215-1744 Rev. D; ECN 18-05-022
Local codes may require the installation of a backflow prevention
valve to complete proper installation. Backflow prevention valves
are not included with the fixture and may be supplied by the
contractor or purchased from Bradley Corporation.