ELECTRODE-DEFLECTOR POSITIONING

After mounting the choke (or chokes), check the correct position of the electrodes and deflector, following the listed speci-
fications (mm). It is advisable to check the specifications after each intervention on the combustion head.

OPERATION CYCLE

Thermostat room temperature - furnace
Motor
Transformer
Electromagnetic valve 1° flame
Thermostat modulation
Air flow control
Electromagnetic valve 2° flame
Photo resistance
A
- starting the furnace
B
- presence of flame
C
- end of starting procedure
C-D
- normal operation
D
- thermostat shut-down (TA-TC)
All manuals and user guides at all-guides.com
- 0
4
+1
T1
pre-ventilation time
T2
safety cut-off time
T3
pre-ignition time
T3n
post-ignition time
- 31
5
6
+ 0
65
+ 0,5
-
LMO 44
26 sec.
5 sec.
25 sec.
5 sec.