Pressotronik PT77

8 Menu Sequence Overview

Main menu
Submenu 1
Configuration
P__i
Shortcut
or 60s no action:
Equipment configuration
Exit main/submenu
____
Display
____
Measurement display
____
Pressotronik
Out 1
PrES
Pressure main menu
Settings menu OUT1
Out x
Settings menu OUTx
Analog Out1
Settings menu Analog 1
Exit
Exit menu level
Basic EF
b. E F
Reset
Basic ext. functions
Factory preset
Set Error handling
Error handling
Set Unit Press
Pressure unit
Set Upper
Set max. pressure
reassign O1
Assignment Out 1
reassign O2
Assignment Out 1
Display Rate
Display rate
Turn
Installation direction
Lock Device
Keylock
Exit
Exit menu level
Diagnostic
diA
Journal Out
Diagnostics menu
Log output
Max/Min Press
Max/Min memory
Set Journal Out
Output monitoring
Delay MM
Min/max delay
Exit
Exit menu level
E
Exit
Exit menu level
BX130003 ◦ 02/2021
Submenu 2
Submenu 3
+
____
out1
SP1
____
FH1
F1. H i
____
Switching point 1
____
rP1
FL1
F1. L o
____
Switch-back point 1
____
EF 1
EF1
Delay SP 1
Extended functions
Delay OUT1 On
Delay RP 1
Delay OUT1 Off
Set Out 1
Definition OUT1
Check Out 1
Functional test OUT1
LED Out 1
Function status LED1
Exit
Exit menu level
Exit
E
____
Exit menu level
out_
____
See menu structure Out1
Not applicable for version with
analogue output
____
____
An1
Analog Max1
A1. H i
Maximum value assignment
____
Analog Min1
A1. L o
Minimum value assignment
Set A.Out1
____
A. o u1
Output function
____
Check An1
C. A n1
Functional test Analog 1
____
Exit
E
Exit menu level
E
rES
Err. h
P. u ni
P. H i
r. o u 1
r. o u 2
di5
turn
Loc
E
J. o ut
P. M M
SJ. o u
DP. M M
E
Settings and Display Menu
____
Switch
____
Change measurement display to show details for the unit
MBAR - PSI
MBAR
available when max. pressure (P.Hi) <=10 bar
____
Selection menu
____
SP1
Switching point setting /
FI. H i
Assigns a value to frequency 100 Hz (only OUT1 and OUT2)
0b - < P. H i >
Selection menu
____
____
rP1
Set switch-back point /
FI. L o
Assigning a value to frequency 1 Hz (only OUT1 and OUT2)
0b - < P. H i >
dS1
____
Selection menu
____
___
Amount of time the signal must be present for output OUT1 to trigger.
0 - 100
Setting range: 0...100 seconds (for frequency output without function)
____
Selection menu
____
dr1
___
Amount of time the signal must be present for output OUT1 to switch back.
0 - 100
Setting range: 0...100 seconds (for frequency output without function)
Definition of switching characteristics for output 1:
____
____
ou1
Selection menu
___
Hno Hnc Hysteresis function NO contact or NC contact
Hno - FM
Fno Fnc Window function NO contact or NC contact /
n. o P
Normal switching output operation
____
____
C. o u1
Selection menu
____
oFF
Switching output Off /
n. o p - on
on
Switching output On /
____
Selection menu
____
LEd1
L=__
LED = output: follows switching output
L= o
L= o - L=-o
L=-o
LED = -output: inverted to switching output
____
E
____
Selection menu
____
Sets the maximum analogue output signal to a defined value.
(Note: Max. – Min >= 10 % of the measuring range)
0b - < P. H i >
____
Selection menu
____
Sets the maximum analogue output signal to a defined value.
0b - < P. H i >
(Note: Max. – Min >= 10 % of the measuring range)
____
Selection menu
_ _
Selecting the analogue output function:
i I
4...20 mA
i 1 - u 3
____
Selection menu
____
n. o P
Analogue output normal mode /
HALF
Output mean analogue value /
n. o P - Lo
Alternate menu for version with analogue output
Not applicable when ordered with 2 or more switching outputs
____
Confirm
___
Resets the device to factory configuration
no - YES
____
____
Confirm
___
Disable/enable normal error handling and analysis
no - YES
Selecting the pressure unit displayed
____
Selection menu
___
The measuring range will automatically be adjusted.
MBAR- PSI
MBAR
available when max. pressure (P.Hi) <=10 bar
Selection menu
____
____
Configures the maximum pressure for the connected sensor.
(Example: sensor maximum measuring range 100 bar)
0 - P. H i
Selection menu
____
____
Assign switching output Out1 to function pressure(temp/level) or as error signal
Err - PrES
____
Selection menu
___
Assign switching output Out2 to function pressure(temp/level) or as error signal
Err - Pres
____
Selection menu
____
Selecting the display refresh rate:
FASt - off
FASt [fast], Medi [medium], SLo [slow],
Selection menu
____
___
Rotates the display 180°
no - YES
____
Selection menu
___
Activating the keylock by entering a numerical code > 0 Master code 287
0 - 999
____
Selection menu
____
Displays the last 6 alarms + delete function.
Jor I - ---
Display:
JorX
____
Selection menu
Displays limits + delete function.
____
___; _ - ---
Display: Value – time passed in hours/days; toggle values and time ▲▼
____
Selection menu
out_
Selecting the alarm output to be logged
Out1 - Out_
____
Selection menu
___
Amount of time the signal must be present before saving the maximum / minimum value.
Setting range: 0...100 seconds
0 - 100
MBAR BAR MPA PSI
FH1 Define maximum window limit
FL1 Set lower window limit
FM
Frequency output 1-100 Hz
F1
Simulation 1 Hz
F100
Simulation 100 Hz
u 1
2...10 V
u 2 0...10 V
u 3 0...5 V
Hi Output maximum analogue value
Lo Minimum analogue value output
MBAR [mbar],
BAR
[bar],
MPA
oFF [Display off]
X – time passed in hours/days; toggle alarms ▲▼
Bühler Technologies GmbH
[Mega Pascal], PSI[psi]
13