Safety
Safety instructions
Make sure that any person installing, taking into operation
and operating the contactless liquid level indicators:
• Is technically qualified and competent.
• Fully complies with these assembling instructions.
Improper operations or misuse could cause danger to:
• life and limb
• the equipment and other assets of the operator
• the equipment proper function
Safety instructions in this manual are shown in three diffe-
rent forms to emphasize important information.
WARNING
This information indicates particular danger to life and health.
Disregarding such a warning can lead to serious or fatal injury.
CAUTION
This information indicates particular danger to equipment and/
or other property of the user. Serious or fatal injury cannot be
excluded.
This notes give important or specific information concerning the
equipment.
Safety notes on the equipment operation
Electrical installation is subject to the relevant national
safety rules.
It is mandatory to connect the grounding cable because of
safety reason.
CAUTION
Installation, electrical connection and fitting the device have to
be carried out by qualified personnel and only in accordance to
this instruction manual.
It is responsibility of the user to make sure that the device is
used for specified application only.
For safety matters, please avoid any unauthorized and
improperly works.
WARNING
All relevant fire protection regulation must be strictly observed.
4
NOTE
CONTACTLESS LIQUID LEVEL INDICATORS CU eOLI100/ CU eOLI200
Product description
The Contactless Ultrasonic CU eOLI is used for mea-
surement of the oil level for transformer equipped with
conservator (with or without rubber bag). It is consists of
an embed ultrasonic sensor: the conservator oil level (%)
can be read throught the analog output 4-20mA (COMEM
can provide also the Viewer to visualize the value at
human height.) and through the digital output (MODBUS
RS-485). Note that every ultrasonic sensor has an offset
that creates a blind zone in which the sensor is not able
to measure. See installation paragraph to determine the
correct position of the Contactless Ultrasonic CU eOLI, in
order to minimize the blind zone inside the conservator.
A configurable changeover relay can switch in case of mis-
sing power supply, reaching of top and bottom thresholds,
or in both the cases.
Figure 1
Note:
* equal to: 120mm for CueOLI100/ 200mm for CUeOLI200
** in absence of installation offset (without rubber bag) MAX VALUE (%) is equal
to: (conservator diameter - blind zone)*100/ conservator diameter
It is important to observe the limit values indicated on the
nameplate and in the manual before commissioning the device.
WARNING