Installation
Installation on the conservator
The Contactless Ultrasonic CU eOLI must be installed on
the top of the conservator, in vertical position, in the center
of the conservator, far from the sides.
Figure 2
Heigt of the conservator
CU eOLI100:
120 -1000mm
Reading area
250mm
CAUTION
The operating and the installation requirements described in
this manual must be strictly following. If not, the device can be
damaged or a malfunction can occur.
The Contactless Ultrasonic CU eOLI is provided with a pla-
nar gasket with dimensions of 100mm x 70mm x 4mm. It
has to be inserted between the CU eOLI flange and a cross
pipe connector- with inner diameter > 27mm, over the con-
servator, having an appropriate seat for the gasket. Fix the
CU eOLI to the cross pipe connector over the conservator
with M16 screws, washer and nuts.
Inner diameter > 27mm
Cross pipe
connector
Figure 3
CU eOLI200:
200-2000mm
500mm
Gasket
Seat for the gasket
Positioning without rubber bag
In order to not affect the correct measurement setup,
the Contactless Ultrasonic CU eOLI must be installed
following these prescriptions on the dimensions Ø (dia-
meter of the cross pipe connector) and h (sensor offset:
distance between the top of the conservator and the
sensor). Select the combination (Ø-h) using the following
chart. By default, the CU eOLI is provided ready for the
recommended setup.
Sensor offset (mm) - pipe installation
Sensor offset (mm) - pipe installation
110
105
100
95
DENIED VALUES
90
85
80
75
70
65
60
55
50
45
40
35
30
30
50
Recommended setup
ф= 50mm
h= 60mm
Graph 1
Sensor offset (mm) - pipe installation
Sensor offset (mm) - pipe installation
115
110
105
100
95
DENIED VALUES
90
85
80
75
70
65
60
55
50
45
40
35
30
30
50
Recommended setup
ф= 65mm
h= 60mm
Graph 2
Figure 4
ALLOWED VALUES
65
φpipe (mm)
Values valid for CU 100
ALLOWED VALUES
65
φpipe (mm)
Values valid for CU 200
75
75
5