If the room temperature is lower than the desired value, it is advisable to set a higher order curve and vice versa. Pro-
ceed by increasing or decreasing in steps of one and check the result in the room.
90
10
85
80
70
60
50
40
30
20
20
10
fig. 31- Compensation curves
This parameter is used only if the time programming has been activated. See "Time programming" on page
A
301
Outside Temperature Heating OFF
Access the "Out Temp Heat Off" to activate the function: between 7°C and 30°C.
If activated, this function will deactivate the heating demand whenever the temperature measured by the external probe
is higher than the programmed value.
The heating demand will be reactivated as soon as the temperature measured by the external probe is lower than the
programmed value.
Adjustments from remote timer control
If the boiler is connected to the Remote Timer Control (optional), the previously described adjustments are
A
managed as described in table 1.
Table 1
Heating temperature adjustment
DHW temperature adjustment (with
optional hot water tank installed)
Summer/Winter Switchover
Eco/Comfort selection (with optional
hot water tank installed)
Sliding Temperature
306
9
8
7
6
5
4
3
2
1
0
-10
-20
Adjustment can be made from the Remote Timer Control menu and the boiler control panel.
Adjustment can be made from the Remote Timer Control menu and the boiler control panel.
Summer mode has priority over a possible Remote Timer Control heating request.
On disabling DHW from the Remote Timer Control menu, the boiler selects Economy mode.
In this condition, the button detail 10 - fig. 1 on the boiler panel, is disabled.
By enabling DHW from the Remote Timer Control menu, the boiler selects Comfort mode. In
this condition, use the button detail 10 - fig. 1 on the boiler panel to select one of the two
modes.
Both the Remote Timer Control and the boiler card manage the Sliding Temperature adjust-
ment: between the two, the Sliding Temperature of the boiler card has priority.
cod. 3541V120 - Rev 00 - 09/2021
90
10
85
80
70
60
50
40
30
20
90
8
6
9
7
10
85
80
70
60
50
40
30
20
fig. 32- Example of compensation parallel curve offset
MACH
9
8
7
6
5
4
3
2
1
5
3
4
2
1
EN