Siemens 3TH40 Instrucciones De Servicio página 2

Ocultar thumbs Ver también para 3TH40:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 3
Contactor Relay
Instructions
Limited protection against contact with live parts
Degree of protection IP 20 to IEC 60529
!
Safe from finger touch to DIN VDE 0106, Part 100
Commissioning and maintenance by qualified personnel only.
Follow the operating instructions.
WARNING:
HAZARDOUS VOLTAGE
CAN CAUSE ELECTRICAL SHOCK
DISCONNECT POWER BEFORE PROCEEDING
WITH ANY WORK ON THIS EQUIPMENT.
Installation
For dimension drawings see Fig. I (dimensions in mm).
> With screw terminals
> Fig. I a
a.c. operated
> Fig. I b
d.c. operated
> With tab connectors
> Fig. I c
a.c. operated
> Fig. I d
d.c. operated
Minimum clearances from earthed parts: 8 mm
Snap onto 35 mm standard mounting rail to DIN EN 50 022 or fix on a
plain surface with two M4 screws. With screw mounting, always use
plain washers and spring washers.
Cover the contactors during installation if foreign particles, such as
swarf, can fall onto them. Install contactors in a housing if they are
exposed to dirt, dust or aggressive atmospheres.
For permissible mounting positions see
> Fig. ¬ a
a.c. operated
> Fig. ¬ b
d.c. operated
Connection
The terminal screws can be tightened with a power screwdriver.
Screwdriver blade width: 5 to 6 mm
Permissible conductor cross>sections
Solid
Finely stranded, with end sleeve
Push>on receptacle B 2,8
AWG wires
Tightening torque
Use 75 ∞C copper wire only.
For circuit diagrams (examples) see Fig. √.
> Fig. III a
3TH40
4NO/3NO+1NC/2NO+2NC
> Fig. III b
3TH42
8NO/7NO+1NC/6NO+2NC
> Fig. III c
3TH43
10NO/9NO+1NC/8NO+2NC
Operation
Observe operating voltage (see rating plate of magnet coil).
The operating state of the contactor is shown at the position indicator;
see Fig. IV.
2
AND BURNS.
2¥0.5 to 1 mm
2
2¥1 to 2.5 mm
2
1¥4 mm
2
2¥0.75 to 2.5 mm
2
2¥0.3 to 1.5 mm
2
2¥AWG 18 to 12
0.8 to 1.4 Nm/7 to 12 lb
Order No.: 3ZX1012>0TH01>1BA1
Maintenance
The following components can be replaced: magnet coil
For Order Nos. see Catalog NSK.
Only use of original spare parts ensures the operational safety of the
contactors.
Cleaning
Remove dust by suction.
Magnet coil
For coil replacement see
> Fig. V a
a.c. coil
> Fig. V b
d.c. coil
Ensure that the pole faces of the magnet coil are clean. Do not use grease
solvents or sharp objects for cleaning.
Technical Data
Permissible ambient temperature
> Operation
> Storage
Rated insulation voltage U i
Rated operational current I e /AC>12/AC>1
With screw terminals
Rated operational voltage
> 230 V
> 240 V
> 400 V
> 415 V
> 500 V
> 690 V
Rated operational voltage
> 24 V
> 48 V
> 110 V
> 220 V
> 440 V
> 600 V
With tab connectors
Rated operational voltage
> 230 V
> 240 V
> 400 V
> 415 V
> 500 V
Rated operational voltage
.
in
> 24 V
> 48 V
> 110 V
> 220 V
> 440 V
Short>circuit protection:
> Fuse>links
NEOZED and DIAZED, gL (gG)
> Circuit>breaker, C>char.
For further data and accessories see Catalog NSK.
3TH40, 3TH42, 3TH43
DIN VDE 0660, IEC 60947
> 25 to+55 ∞C
> 50 to+80 ∞C
AC 690 V
A
16
Rated operational
current I e /AC>15/AC>11
A
10
A
10
A
6
A
4
A
4
A
2
Rated operational
current I e /DC>13/DC>11
A
10
A
5
A
0.9
A
0.45
A
0.25
A
0.2
Rated operational
current I e /AC>15/AC>11
A
8
A
8
A
6
A
4
A
4
Rated operational
current I e /DC>13/DC>11
A
8
A
5
A
0.9
A
0.45
A
0.25
A
16
A
16

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

3th423th43

Tabla de contenido