DYNAMIC
BALANCING VALVES
ART.6544DN
Step
Display
6
*
7
*
8
*
9
*
10
*
11
*
12
*
13
*
Via Cavallera 6/A (Loc. Barco) - 25045 Castegnato (Bs) - Italy
Description
Select minimum control value.
*scrolling top:
SET MINIMUM LIMIT
Select maximum control value.
*scrolling top:
SET MAXIMUM LIMIT
Select feedback signal.
*scrolling top:
SELECT FEEDBAC SIGNAL
Set the designed maximum flow.
Accuracy: Greatest of either ±5% of de-
signed max. flow or ±2% of max. valve flow.
*scrolling top:
SELECT MAXIMUM FLOW
Select direction of rotation.
*scrolling top:
SELECT ROTAT DIRECT
Select actuator mode.
*scrolling top:
actuator mode
Activation of password.
*scrolling top:
ACTIVAT PASS WORD
Select direction of rotation when Failsafe.
*scrolling top:
SELECT FAIL SAFE DIRECT
TIEMME Raccorderie S.p.A.
Tel +39 030 2142211 R.A. - Fax +39 030 2142206
info@tiemme.com - www.tiemme.com
EN
Values
Volt default: 2.
Options: from 0-7. Increment: 0.1.
mA default: 4.
Options: from 0-14. Increment: 0.2.
NA if Digital (in step 5).
Volt default: 10.
Options: from 3-10 and at least 3 VDC
greater than the selected minimum limit.
Increment: 0.1.
mA default: 20.
Options: from 6-20 and at least 6 mA
greater than the selected minimum limit.
Increment: 0.2.
NA if Digital (in step 5).
Default: AU; Automatic match of
control signal if analog.
Options: 0-10 VDC, 2-10 VDC or 4-20
mA or AU.
If Digital (in step 5) AU is not an option.
Default: Maximum setting.
Values depend on valve model and unit
scale chosen in step 2 and 3.
Stepping increments as per tech note.
Default: Normally Closed (NC).
Options: Normally Open (NO) or Nor-
mally Closed (NC).
Default: Linear flow.
Options: Linear flow, Equal percentage,
Linear rotation or Linear signal.
For SM.1 and SM.2 only linear rotation
will apply.
Default: Disable.
Options: Enable or Disable.
If Enabled password is required to ac-
cess alarm and programming menu.
Default: Closed.
Options: Open or Closed.
Only valid for SM.0.0.0.4 (failsafe
model). Failsafe direction open means
opening to max. flow
chosen in step 9.
ORIGINAL ITALIAN TRADEMARK
13