TiEmme 6544DN Manual Del Usuario página 14

Válvulas de equilibrio dinámico
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 17
DYNAMIC
BALANCING VALVES
ART.6544DN
In Operation
Display
Information
Control signal
Feedback signal
Valve
Pressure range
Maximum flow rate
Operational direction
Actuator mode
Critical Alarm
Note 1: The flow rate shown on the actuator display is a calculated value. Flow rates below 1.0 valve rotation is shown as indications,
illustrated with an apostrophe in front of the flow rate. If display shows "NA" the valve model has not been chosen in programming menu step 2.
Via Cavallera 6/A (Loc. Barco) - 25045 Castegnato (Bs) - Italy
Description
Indicates unit scale system.
Indicates battery level.
Alarm indicator.
Information
1
Current flow rate
.
Indicates current flow rate in
l/sec, l/hr or GPM.
Indicates value of control signal.
Indicates value of feedback signal.
Indicates valve model.
Indicates pressure range.
Indicates selected maximum de-
signed flow rate.
Indicates direction of rotation.
Indicates control mode
Indicates alarm error code.
TIEMME Raccorderie S.p.A.
Tel +39 030 2142211 R.A. - Fax +39 030 2142206
info@tiemme.com - www.tiemme.com
EN
Values
l/sec or l/min or GPM.
mA or VDC.
Basic version with no battery (SM.0.0.0.3)
Failsafe version with battery (SM.0.0.0.4)
Battery level low, charging needed.
Medium battery level.
Battery charged.
Blinking if actuator is still functional (warning).
Fully on if actuator is not working (critical).
CONTROL SIGNAL 2.0 VDC
FEEDBAC SIGNAL 2.0 VDC
VALVE SM. 3.1
pressur range 30-800 kpad
MAXIMUM FLOW RATE 6.580 L/SEC
OPERAT DIRECT NC
ACTUAT.MODE LIN flo
FAIL SAFE DIRECT CLOSE
ERROR CODE 01
Use
to go to next information line and
to the previous.
0-10 VDC or 0-20 mA or Open/Stop/Close
0-10 VDC or 0-20 mA
SM.1.1, SM.2.1...
32-320 kPaD, 40-320 kPaD.....
Depends on valve etc.
l/sec, l/hr or GPM
NO or NC
Linear flow, Equal percentage, Linear rotation or
Linear signal
01, 03, 05 (without failsafe) or 06.
Only if critical alarm is present.