When any malfunction is occurred, immediately switch off the power supply to the unit, and contact the local dealer, if
necessary. Some simple troubleshooting tips are given below :
SYMPTOMS
1. Compressor does
• No power supply.
not start.
• Fuses blown or automatic circuit break-
• Defective contactor or coil.
• Unit is stopped because safety device has
• Loose wires.
• Compressor faulty.
2. Fan does not work.
• No power supply.
• Fan motor faulty.
• Thermostat setting too high.
3. Unit does work,
• Condenser coil dirty.
but insufficient
• Obstacle blocking air inlet or outlet of the
cooling.
• Insufficient refrigerant in the system.
• Improper water flow rate.
• Water in the system is contaminated.
• No water in the system.
4. Flow Switch Error
• Low water level in the system.
Troubleshooting must be performed by qualified personnel.
All manuals and user guides at all-guides.com

TROUBLESHOOTING

POSSIBLE CAUSES
down open.
tripped.
unit.

! ! ! ! ! CAUTION

REMEDIAL ACTION
• Check power supply.
• Look for short circuit or grounded wires in
motor windings. Replace fuses and reset
circuit breakers when the fault has been
corrected. Check tightness and soundness of
all electrical connections.
• Repair or replace.
• Determine the type of safety shut down and
correct the default before the unit is restarted.
• Check wire connections and tighten terminal
screws.
• Contact local dealer.
• Check power supply.
• Contact local dealer.
• Reset thermostat.
• Contact local dealer.
• Remove the obstacle.
• Contact local dealer.
• Contact local dealer.
• Contact local dealer.
• Check water supply.
• Check water supply.