PARAMETER SETTING – MONITORING 
3.1.
Parameters 
Relative vacuum: no setting = 10 mbar 
Original 
No 
Parameter 
setting 
Motor A hour counter 
Motor B hour counter 
Motor C hour counter 
Fan cut‐in threshold 
25°C 
High pressure 
‐850 mbar 
Low pressure 
‐650 mbar 
Top‐up pressure 
‐570 mbar 
3rd backup pressure 
‐550 mbar 
Control alarm pressure 
‐500 mbar 
Low network alarm pressure 
‐370 mbar 
High network pressure contact 
‐880 mbar 
On/off motor delay 
0 s 
"A" motor presence 
On 
"B" motor presence 
On 
"C" motor presence 
On 
Forced running 
15 minutes 
The display in relative mbar will use the formula P (absolute) = P (relative) + 1010 mbar 
Absolute vacuum: no setting = 10 mbar 
Original 
No 
Parameter 
setting 
Motor A hour counter 
Motor B hour counter 
Motor C hour counter 
Fan cut‐in threshold 
25°C 
High pressure 
160 mbar 
Low pressure 
360 mbar 
Top‐up pressure 
440 mbar 
3rd backup pressure 
460 mbar 
Control alarm pressure 
510 mbar 
Low network alarm pressure 
640 mbar 
High network pressure contact 
110 mbar 
On/off motor delay 
0 s 
"A" motor presence 
On 
"B" motor presence 
On 
"C" motor presence 
On 
Forced running 
15 minutes 
519112‐02 
Increment 
Setting range 
value 
The "motor X hour counter" parameters are only updated 
when the corresponding engine is running. 
Precision is to within 1 second 
from 10°C to 35°C 
1°C 
from –999 mbar to –90 mbar 
10 mbar 
from +20 of high pressure to –70 mbar 
10 mbar 
from +20 of low pressure to –50 mbar 
10 mbar 
from +10 of top‐up pressure to –40 mbar 
10 mbar 
rd
from +20 of 3
 backup/top‐up pressure to ‐20 
10 mbar 
from +20 of control alarm network to 0 
10 mbar 
from –999 mbar to high pressure 
10 mbar 
from 0 s. to 20 s. 
1 second 
On or Off 
‐‐ 
On or Off 
‐‐ 
On or Off 
‐‐ 
From 0 to 30 minutes 
1 minute 
Increment 
Setting range 
value 
The "motor X hour counter" parameters are only updated 
when the corresponding engine is running. 
Precision is to within 1 second 
from 10°C to 35°C 
1°C 
from 11 mbar to 920 mbar 
10 mbar 
from +20 of high pressure to 940 mbar 
10 mbar 
from +20 of low pressure to 960 mbar 
10 mbar 
from +10 of top‐up pressure to 970 mbar 
10 mbar 
rd
from +20 of 3
 backup/top‐up pressure to 990 
10 mbar 
from +20 of control alarm pressure to 1010 
10 mbar 
from 11 mbar to high pressure 
10 mbar 
from 0 s. to 20 s. 
1 second 
On or Off 
‐‐ 
On or Off 
‐‐ 
On or Off 
‐‐ 
From 0 to 30 minutes 
1 minute 
CYCLIC 2020 
Compressed air: no setting = pressure 0.1 bar / temperature 1°C 
No 
Parameter 
Hysteresis 
Motor A hour counter 
Motor B hour counter 
Motor C hour counter 
Fan cut‐in threshold 
2°C 
High pressure 
5 mbar 
Low pressure 
5 mbar 
Top‐up pressure 
5 mbar 
3rd backup pressure 
5 mbar 
Control alarm pressure 
5 mbar 
Cylinder backup pressure 
5 mbar 
Network alarm min. pressure 
50 mbar 
Network alarm max. pressure 
‐‐ 
Hygrometry 
‐‐ 
Cylinders activation 
‐‐ 
On/off motor delay 
‐‐ 
Number of cylinders sensors 
‐‐ 
"A" motor presence 
"B" motor presence 
"C" motor presence 
These parameters are saved then restored each time the system is switched on. 
Hysteresis 
The number corresponds to the left‐hand digit (green) on the display unit. 
 
3.2.
Setting the parameters 
2°C 
 
5 mbar 
Press the 
and 
simultaneously for 2 seconds. 
 
 
5 mbar 
The  left‐hand  digit  (green)  indicates  the  number  of  the  parameter  and  the  5  right‐hand  digits  (red)  indicate  its 
5 mbar 
value. 
5 mbar 
Use the 
and 
keys to scroll through the parameters in either direction. 
5 mbar 
 
 
5 mbar 
Once positioned on the parameter, set its value using the 
50 mbar 
‐‐ 
Once the value has been set, use the 
‐‐ 
To quit parameter setting mode, press the 
‐‐ 
‐‐ 
Alternatively, if no key has been pressed for 30 seconds, the display returns to normal (left‐hand digit off). 
‐‐ 
 
Original 
Original 
Setting 
Setting 
Setting range 
15 bar 
11 bar 
The "motor X hour counter" parameters are only updated 
when the corresponding engine is running. 
Precision is to within 1 second 
25°C 
25°C 
from 10°C to 35°C 
11.5 bar 
9.5 bar 
from 1.6 to 15 bar 
10 bar 
9 bar 
from 1.1 to –0.5 of high pressure 
9.5 bar 
8.5 bar 
from 0.9 to –0.2 of low pressure 
9 bar 
8 bar 
from 0.9 to –0.2 of top‐up pressure 
rd
8.5 bar 
7.5 bar 
from 0.7 to –0.2 of 3
 backup pressure 
100 bar 
100 bar 
from 0 to 200 bar or 250 bar (according to SW1‐1) 
6.3 bar 
4.5 bar 
from 0 to –0.5 bar of control alarm pressure 
12.5 bar 
10 bar 
from 0.1 to 15 bar 
‐45°C 
‐45°C 
from –80°C to 0°C 
7.5 bar 
7 bar 
from 0.1 to 15 bar 
0 s 
0 s 
from 0 s. to 20 s. 
from 0 to 2 
On 
On 
On or Off 
On 
On 
On or Off 
On 
On 
On or Off 
and 
keys: the digits start flashing. 
 
 
and 
keys to move on to the preceding or following parameter. 
 
 
and 
keys simultaneously for 2 seconds. 
 
 
Increment 
Hysteresis 
value 
1°C 
2°C 
0.1 bar 
0.1 bar 
0.1 bar 
0.1 bar 
0.1 bar 
0.1 bar 
0.1 bar 
0.1 bar 
0.1 bar 
0.1 bar 
1 bar 
3 bar 
0.1 bar 
0.1 bar 
0.1 bar 
0.5 bar 
1°C 
2°C 
0.1 bar 
0.1 bar 
1 second 
‐‐ 
‐‐ 
‐‐ 
‐‐ 
‐‐ 
‐‐ 
‐‐ 
‐‐ 
16 