3.
PARAMETER SETTING – MONITORING
3.1.
Parameters
Relative vacuum: no setting = 10 mbar
Original
No
Parameter
setting
A
Motor A hour counter
0
b
Motor B hour counter
0
C
Motor C hour counter
0
t
Fan cut‐in threshold
25°C
0
High pressure
‐850 mbar
1
Low pressure
‐650 mbar
2
Top‐up pressure
‐570 mbar
3
3rd backup pressure
‐550 mbar
4
Control alarm pressure
‐500 mbar
5
Low network alarm pressure
‐370 mbar
6
High network pressure contact
‐880 mbar
r
On/off motor delay
0 s
A
"A" motor presence
On
b
"B" motor presence
On
C
"C" motor presence
On
H
Forced running
15 minutes
The display in relative mbar will use the formula P (absolute) = P (relative) + 1010 mbar
Absolute vacuum: no setting = 10 mbar
Original
No
Parameter
setting
A
Motor A hour counter
0
b
Motor B hour counter
0
C
Motor C hour counter
0
t
Fan cut‐in threshold
25°C
0
High pressure
160 mbar
1
Low pressure
360 mbar
2
Top‐up pressure
440 mbar
3
3rd backup pressure
460 mbar
4
Control alarm pressure
510 mbar
5
Low network alarm pressure
640 mbar
6
High network pressure contact
110 mbar
r
On/off motor delay
0 s
A
"A" motor presence
On
b
"B" motor presence
On
C
"C" motor presence
On
H
Forced running
15 minutes
519112‐02
Increment
Setting range
value
The "motor X hour counter" parameters are only updated
when the corresponding engine is running.
Precision is to within 1 second
from 10°C to 35°C
1°C
from –999 mbar to –90 mbar
10 mbar
from +20 of high pressure to –70 mbar
10 mbar
from +20 of low pressure to –50 mbar
10 mbar
from +10 of top‐up pressure to –40 mbar
10 mbar
rd
from +20 of 3
backup/top‐up pressure to ‐20
10 mbar
from +20 of control alarm network to 0
10 mbar
from –999 mbar to high pressure
10 mbar
from 0 s. to 20 s.
1 second
On or Off
‐‐
On or Off
‐‐
On or Off
‐‐
From 0 to 30 minutes
1 minute
Increment
Setting range
value
The "motor X hour counter" parameters are only updated
when the corresponding engine is running.
Precision is to within 1 second
from 10°C to 35°C
1°C
from 11 mbar to 920 mbar
10 mbar
from +20 of high pressure to 940 mbar
10 mbar
from +20 of low pressure to 960 mbar
10 mbar
from +10 of top‐up pressure to 970 mbar
10 mbar
rd
from +20 of 3
backup/top‐up pressure to 990
10 mbar
from +20 of control alarm pressure to 1010
10 mbar
from 11 mbar to high pressure
10 mbar
from 0 s. to 20 s.
1 second
On or Off
‐‐
On or Off
‐‐
On or Off
‐‐
From 0 to 30 minutes
1 minute
CYCLIC 2020
Compressed air: no setting = pressure 0.1 bar / temperature 1°C
No
Parameter
Hysteresis
A
Motor A hour counter
b
Motor B hour counter
C
Motor C hour counter
t
Fan cut‐in threshold
2°C
0
High pressure
5 mbar
1
Low pressure
5 mbar
2
Top‐up pressure
5 mbar
3
3rd backup pressure
5 mbar
4
Control alarm pressure
5 mbar
5
Cylinder backup pressure
5 mbar
6
Network alarm min. pressure
50 mbar
7
Network alarm max. pressure
‐‐
8
Hygrometry
‐‐
9
Cylinders activation
‐‐
r
On/off motor delay
‐‐
P
Number of cylinders sensors
‐‐
A
"A" motor presence
b
"B" motor presence
C
"C" motor presence
These parameters are saved then restored each time the system is switched on.
Hysteresis
The number corresponds to the left‐hand digit (green) on the display unit.
3.2.
Setting the parameters
2°C
5 mbar
Press the
and
simultaneously for 2 seconds.
5 mbar
The left‐hand digit (green) indicates the number of the parameter and the 5 right‐hand digits (red) indicate its
5 mbar
value.
5 mbar
Use the
and
keys to scroll through the parameters in either direction.
5 mbar
5 mbar
Once positioned on the parameter, set its value using the
50 mbar
‐‐
Once the value has been set, use the
‐‐
To quit parameter setting mode, press the
‐‐
‐‐
Alternatively, if no key has been pressed for 30 seconds, the display returns to normal (left‐hand digit off).
‐‐
Original
Original
Setting
Setting
Setting range
15 bar
11 bar
0
0
The "motor X hour counter" parameters are only updated
0
0
when the corresponding engine is running.
Precision is to within 1 second
0
0
25°C
25°C
from 10°C to 35°C
11.5 bar
9.5 bar
from 1.6 to 15 bar
10 bar
9 bar
from 1.1 to –0.5 of high pressure
9.5 bar
8.5 bar
from 0.9 to –0.2 of low pressure
9 bar
8 bar
from 0.9 to –0.2 of top‐up pressure
rd
8.5 bar
7.5 bar
from 0.7 to –0.2 of 3
backup pressure
100 bar
100 bar
from 0 to 200 bar or 250 bar (according to SW1‐1)
6.3 bar
4.5 bar
from 0 to –0.5 bar of control alarm pressure
12.5 bar
10 bar
from 0.1 to 15 bar
‐45°C
‐45°C
from –80°C to 0°C
7.5 bar
7 bar
from 0.1 to 15 bar
0 s
0 s
from 0 s. to 20 s.
0
0
from 0 to 2
On
On
On or Off
On
On
On or Off
On
On
On or Off
and
keys: the digits start flashing.
and
keys to move on to the preceding or following parameter.
and
keys simultaneously for 2 seconds.
Increment
Hysteresis
value
1°C
2°C
0.1 bar
0.1 bar
0.1 bar
0.1 bar
0.1 bar
0.1 bar
0.1 bar
0.1 bar
0.1 bar
0.1 bar
1 bar
3 bar
0.1 bar
0.1 bar
0.1 bar
0.5 bar
1°C
2°C
0.1 bar
0.1 bar
1 second
‐‐
1
‐‐
‐‐
‐‐
‐‐
‐‐
‐‐
‐‐
16