4.3.6.
Temperature fault 
When power is switched on, there is a 30‐second temperature fault masking timeout. 
 
If the probe is disconnected, the "high temperature" alarm is activated, the fan is actuated and the display shows 
"tt" when the room temperature is consulted. 
Note: if only the "signal" wire (terminal 49) is disconnected, the value displayed is 67°C. 
If the temperature rises above 45°C, the "temperature fault" 
The "alarm synthesis" relay and the buzzer are activated. 
There is a 5‐second timeout before the fault is taken into account. 
The fault is automatically cleared when the temperature falls below the threshold ‐ hysteresis. 
This alarm has no effect on the motors. 
This fault is stored and can be displayed by pressing the 
 
If the temperature falls below 5°C, the "temperature fault" 
The "alarm synthesis" relay and the buzzer are activated. 
There is a 5‐second timeout before the fault is taken into account 
The fault is automatically cleared when the temperature rises above the threshold + hysteresis. 
This alarm has no effect on the motors. 
This fault is stored and can be displayed by pressing the 
 
If the temperature exceeds the fan cut‐in threshold (parameter "t"), the "fan" relay is activated. 
There is a 5‐second timeout before exceeding of the threshold is taken into account. 
The relay automatically opens when the temperature falls below the threshold ‐ hysteresis (‐2°C). 
 
This has no effect on the motors. 
4.3.7.
Clearing faults 
After  having  noted  the  faults  and  taken  the  necessary  steps,  pressing  the 
simultaneously clears all the faults. The LED goes out, except if there is also a fault. 
519112‐02 
CYCLIC 2020 
 indicator comes on steady. 
 key (LED on). 
 light flashes slowly. 
 key (LED on). 
  and 
  keys 
 
4.3.8.
Electronic card reset and system restart 
Pressing  the 
  and 
  keys  simultaneously  during  2  seconds  resets  the  electronic  card  and 
restarts the system. 
 
5.
JBUS ‐ RS 485 SERIAL LINK 
 
This link allows the main data transfer from CYCLIC 2020 to: 
‐ either a networked remote monitoring system, 
‐ or to one or two REPORT STATUS units, see Manual No.514584. for more detailed information. 
Note:  the  CYCLIC  2020  can't  be  simultaneously  connected  to  a  remote  monitoring  system  and  1  or  2  REPORT 
STATUS units. 
The  CYCLIC  2020  address  can  be  adjusted  from  0  to  F  by  a  coding  wheel  on  the  CYCLIC  2020  board  to  the 
switches. 
The data transferred over the link are read‐only data with an updating interval of 10 seconds. 
 
Link configuration 
 
Data rate: 
9600 bauds 
Format: 
8 data bits 
We hold the JBUS table at your disposal: Manual No.519147. 
 
6.
CONNECTION TERMINAL BLOCK 
 
The switch configuration relates to your electrical diagram. 
 
See diagram on Annex 
 
 
Parity: 
none 
Stop bit: 
1 bit 
20 