 Auto 2 details
Temp switching to cooling ➝ 
Temp switching to heating ➝ 
Outdoor temp setting to limit in cooling ➝ 
Outdoor temp setting to limit in heating ➝ 
 Auto 3 details
Outdoor temp setting to limit in cooling ➝ 
Outdoor temp setting to limit in heating ➝ 
Indoor temp switching to cooling ➝ 
Indoor temp switching to heating ➝ 
All manuals and user guides at all-guides.com
 Auto 2 details
Set the temperatures switching to cooling and heating and the outdoor temp
settings to limit in cooling and heating.
"[Set temp - Temp switching to cooling] < [Indoor return air temp]" and
"[Outdoor temp, cooling] < [Outdoor air temp]" ⇒Operation mode: Cooling
"[Set temp + Temp switching to heating] > [Indoor return air temp]" and
"[Outdoor temp, heating] > [Outdoor air temp]" ⇒Operation mode: Heating
 Auto 3 details
Set the outdoor temp settings to limit in cooling and heating and the indoor
temp settings to limit in cooling and heating.
"[Indoor temp, cooling] < [Indoor return air temp]" and
"[Outdoor temp, cooling] < [Outdoor air temp]"
"[Indoor temp, heating] > [Indoor return air temp]" and
"[Outdoor temp, heating] > [Outdoor air temp]"
— 34 —
30
Selection range of outdoor temp. in cooling
28
26
Thermo-OFF
Temp.diff.
24
22
20
Thermo-OFF
Heating
18
16
14
Selection range of outdoor temp. in heating.
12
10
2 1
14
16
18
20
Outdoor temp.
Forced Thermo-OFF
30
28
Selection range of outdoor temp. in cooling
26
24
22
20
18
Heating
16
14
Selection range of outdoor temp. in heating
12
10
10
12
14
16
18
20
Outdoor temp.
Cooling
Set
temp.
Temp.diff.
Forced Thermo-OFF
22
24
26
28
0 3
⇒Operation mode: Cooling
⇒Operation mode: Heating
Cooling
Forced Thermo-OFF
22
24
26
28
30