Fault
Fault
Possible cause
code
Sensor damaged
Delivery sensor 1
F10
Wiring shorted
fault
Wiring disconnected
Card parameter
F11
Wrong card parameter setting
fault
Card parameter
F12
Wrong card parameter setting
fault
Sensor damaged
Delivery sensor 2
F14
Wiring shorted
fault
Wiring disconnected
Card parameter
F16
Wrong card parameter setting
fault
Supply voltage
F34
Electric mains trouble
under 170V.
Faulty mains fre-
F35
Electric mains trouble
quency
Pressure too low
Incorrect system
F37
water pressure
Sensor damaged
Probe damaged or wiring shorted
F39
External probe fault
Probe disconnected after activating
the sliding temperature
Incorrect system
F40
Pressure too high
water pressure
Delivery sensor not inserted in
A41
Sensor positioning
boiler shell
Heating sensor
F42
Sensor damaged
fault
System water pres-
F47
Wiring disconnected
sure sensor fault
42
EN
ATLAS D ECO 34 COND SI UNIT
Some faults linked to the circulating pump are signalled by the LED located around the
Cure
speed selector (fig. 42 - fig. 43).
Check the wiring or replace
the sensor
Check the card parameter and
modify it if necessary
Check the card parameter and
modify it if necessary
Check the wiring or replace
the sensor
Check the card parameter and
modify it if necessary
Check the electrical system
Table. 7 - Circulating pump LED indications
Check the electrical system
Fill the system
Check the sensor
Check the wiring or replace
the sensor
Reconnect the external sensor
or disable the sliding tempera-
ture
Check the system
Check the safety valve
Check the expansion tank
Check the correct positioning
and operation of the heating
sensor
Replace the sensor
Check the wiring
Circulating pump diagnostics (model PARA)
Some faults linked to the circulating pump are signaled by the LED (fig. 43).
LED
On with red light
Flashing with red
light
Flashing with red/
green light
cod. 3541Q474 - Rev. 00 - 12/2021
fig. 42
Off
Min
.
Circulating pump on STANDBY
1
I
4
II
7
III
Green ON
Circulating pump Working
Green Flashing
Air venting cycle
Green/Red alternating
Circulating pump blocked due to external causes:
- Overvoltage (>270V)
- Insufficient voltage (<160V)
- Motor overload
Red Flashing
Circulating pump blocked due to internal causes:
- Motor blocked
- Damaged electronics
fig. 43
Fault
Cause
Fault
Blocked rotor
Contact/winding
Faulty winding
Supply side voltage too low/
Under/overvoltage
high
Excessive module tem-
Inside of module too hot
perature
Short circuit
Motor current too high
The hydraulic system of
Turbine operation
pumps is fed but the pump
does not have mains voltage
Dry running
Air in pump
The motor turns with difficulty.
Pump operation not in accord-
ance with specifications (e.g.
Overload
high module temperature).
The speed is lower than in
normal operation.
Cure
Activate manual restart or
contact Customer Service
Check the mains voltage
and conditions of use.
Request Customer Service
Check the mains voltage,
the water flow/pressure as
well as the environmental
conditions