Roger B70/2ML Instrucciones Y Advertencias Para El Instalador página 57

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 142
CONTACT
16(AP)
17(COM) Open control signal input (N.O.).
15(CH)
17(COM) Close command input (N.O.).
14(PP)
17(COM) Step by step mode command input (N.O.).
13(PED)
17(COM) Partial open control signal input (N.O.).
RECEIVER CARD
BATTERY CHARGER
B71/BC
BATTERY KIT
2x12 Vdc 1,2 Ah
(B71/BC/INT) *
or
2x12 Vdc 4,5 Ah
(B71/BC/EXT)
Only AGM type.
* only for installations in
BOX
DESCRIPTION
IMPORTANT: persistent activation of the opening command prevents automatic reclosure; the auto
matic reclosure time count is resumed when the opening command is released.
The function of the control is determined by parameter
On double leaf gate automation systems, by default, the partial opening command opens LEAF 1
completely.
With single leaf swing gate installations, by default, partial opening is 50% of total opening.
– PR1
– PR2
display shows
is restored or until the battery voltage drops below the minimum permissible limit. In this case,
(Battery Low) is shown on the display and the control unit accepts no commands.
If mains power is lost while the gate is moving (black out), the gate stops and then automatically
resumes the interrupted manoeuvre after 2 seconds.
Two 12 V DC, 1.2 Ah batteries installed in the automation system itself.
Two 12 V DC, 4.5 Ah batteries installed in an external case.
To reduce battery consumption, the positive power feed wire of the photocell transmitters and re
controller unit disconnects power from the accessory devices when the gate is completely open or
completely closed.
WARNING! the batteries must always be connected to the electronic control unit in order to charge.
Periodically (at least every 6 months), check that the batteries are in good working order.
For more information, refer to the installation manual for the B71/BC battery charger.
.
).
).
or
57

Publicidad

Tabla de contenido
loading

Tabla de contenido