2. PLANNING

2.1 I
NSTALLATION ZONES
Both FIN-180P and FIN-180P-HW units can be installed in climatic zones 1 to 4 as defined by the
Department of Energy (refer to Appendix A for the map), whether as a stand alone unit or connected to the
ducting of an AHU. Installation in any other climatic zone may cause damage to the house.
2.2 I
NSTALLATION TYPES
Always use insulated ducting of a minimum R-4 insulation factor.
2.2.1 S
A
TAND
LONE
The installer shall ensure that, if necessary, an in-line heater sized according to required airflow and outside
design heating temperature from Manual J or ASHRAE table is installed to avoid condensation on
uninsulated duct distribution systems within the house or surfaces near the distribution register. The in-line
heater shall have an integrated airflow sensor and an over temperature sensor to prevent heating in no-flow
or low-flow conditions.
When deciding if a preheater is required and
whether it should be installed BEFORE or
AFTER the supply fan, consider the following:
This supply fan's minimum operating
temperature is 14 °F.
The minimum distance between the
preheater and the supply fan is 12 inches.
The temperature distributed in the ducting
should not be below 55 °F.
2.2.2 I
NSTALLATION WITH AN
The installer shall ensure that, if necessary, an in-line heater sized according to required airflow and outside
design heating temperature from Manual J or ASHRAE table is installed to ensure that the air delivered
to the AHU is never below the minimum temperature allowed by the manufacturer (generally 55 °F). The
in-line heater shall have an integrated airflow sensor and an over temperature sensor to prevent heating in
no-flow or low-flow conditions.
When deciding if a preheater is required and whether it should be installed BEFORE or AFTER the supply
fan, consider the following:
This supply fan's minimum operating temperature is 14 °F.
The minimum distance between the preheater and
the supply fan is 12 inches.
The temperature distributed in the ducting
should not be below 55 °F, unless the
AHU blower is always running when
the supply fan runs. Refer to
section 4.2 for wiring
configurations.
I
NSTALLATION
AHU
CAUTION
Follow AHU
manufacturer's
VJ0150
guidelines for
minimum distance.
5