Technical Data; Accessories; Description - Nederman Fan Starter 11 Manual De Instrucciones

Ocultar thumbs Ver también para Fan Starter 11:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 16

TECHNICAL DATA

Fan Starter
Art. No
Type
Voltage
Suitable Motor
D400/Y690 V
Input fuse
Control voltage
Transformer
Supply to external
equipment
Protection class
Weight
Dimension
H x W x D

ACCESSORIES

Safety/Maintenance switch 6 pole
Running time meter (50 Hz)

DESCRIPTION

Fan Starter 11, 18.5 and 22 are Y/D starters for Nederman NCF Fans.
Y/D starting reduce the start current 3 times compared with a direct start.
The Fan Starter is fitted with a 4-pole main switch interlocked with the door so that
the door can not be opened if the switch is on.
Control voltage is 24 V AC supplied by an internal transformer.
The Fan Starter is prepared for connection with different components in an
extraction system. If Neutral is connected (N) a single-phase supply of 230 V is
available for external equipment, such as FilterMax, MAGNA-system or automatic
dampers. Supply with 24 V AC is also available for Fan Timer or other external 24
V AC equipment.
The 24 V AC can be connected continuously (terminal 3-4) or with S1 in pos.
"AUTO" (terminal 111-112, not available when connected to FilterMax).
11
14514937
400 V 3~(+N) PE 50/60 Hz
4 - 11 kW
Max 35 A
24 V AC, 75 VA
(100 VA available after start of motor.)
230 V AC max 6 A, only if Neutral (N) is
connected
22 kg
Max 15 kW (400V)
Max 18,5 kW (400V)
Fan Starter 11 / 18.5 / 22
18.5
14515037
Y/D start
15 - 18,5 kW
Max 50 A
24 V AC 50/60 Hz
150 VA,
IP 65
500 x 500 x 250
14371983
14372192
14372081
ENGLISH
22
14515537
18,5 - 22 kW
Max 63 A
24 V AC, 50 VA
230 V AC max 6 A,
only if Neutral (N) is
connected
23 kg
5

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Fan starter 18.5Fan starter 22145149371451503714515537

Tabla de contenido