APPENDIX E: charge curve
120%
100%
80%
Amps
60%
40%
20%
0%
Volts
64 32
64 32
16
60 30
60 30
15
56 28
56 28
14
52 26
13
52 26
48 24
12
44 22
11
48 24
40 20
10
Bulk hours
4-stage charging:
Bulk-mode: Entered when charger is started. Constant current is applied until the gassing voltage is reached (14.4V
resp. 28.8V, temperature compensated).
Battery Safe Mode: If, in order to quickly charge a battery, a high charge current in combination with a high absorption
voltage has been chosen, the EasyPlus / EasyPlus will prevent damage due to excessive gassing by automatically
limiting the rate of voltage increase once the gassing voltage has been reached.The Battery Safe Mode is part of the
calculated absorption time.
Absorption-mode: A constant voltage period to fully charge the battery. The absorption time is equal to 20x bulk time
or the set maximum absorption time, whichever comes first.
Float-mode: Float voltage is applied to keep the battery fully charged and to protect it against self-discharge.Reduced
Float: After one day of Float charge a reduced Float charge is applied. This is 13,2V resp. 26,4V (for 12V and 24V
charger). This will limit water loss to a minimum when the battery is stored for the winter season.After an adjustable
time (default = 7 days) the charger will enter Repeated Absorption-mode for an adjustable time (default = 1 hour).
Charge current
Charge voltage
Battery Safe
mode
20 x Bulk-hours or
Max. Absorption time
Absorption
1 day
7 days
7 days
reduced float
1 hour Repeated Absorption
Time