Tabla de contenido

Publicidad

• Technical characteristics
Digital inputs
Voltage:
Current:
Operating conditions
Operating temperature:
Storage temperature:
Humidity:
Max. dissipated power:
Mechanical environment:
Electromagnetic environment:
Relative humidity:

Installation:

Use:
CE Marking
The MF96ORFCDT1 - MF96ORFCMT1 devices comply
with:
• The requirements of the European directe on electromagnetic compatibility (EMC) n° 2014/30/EU
• The low voltage directive n° 2014/35/UE.
• Directive 2011/65/EU modified by directive 2015/863 (RoHS 2).
Electromagnetic compatibility
According to IEC/EN 62052-11 - EN 61326-1
Insulation (EN 61010-1)
Measurement category:
Degree of pollution:
Insulation voltage, Ui:
Impulse withstand voltage
Front surface:
Multifunction Easy Connect
12-24V DC
Max. 10 mA
(-25°C) ÷ (55°C) [-13°F ÷ 131°F]
(-25°C) ÷ (70°C) [-13°F ÷ 158°F]
Suitable for tropical climates
< 5 W
M1
E2
95% not condensing (EN50472-1)
Mounting the KWH-meter in a IP51 switchboard
Indoor
III
2
300V Phase-Earth
- Measuring inputs / Digital I/O inputs
wave 1,2 / 50μs 0,5 J: 6kV
alternate voltage 50Hz / 1 min.: 3kV
- All circuits / earth
alternate voltage 50Hz / 1 min.: 4kV
Class II
NEMO 96 EC
37

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ime mf96orfcdt1Ime mf96orfcmt1Nemo 96 e cMf96orfcdt1Mf96orfcmt1