D200-301-00
WIRELESS OPTICAL SMOKE SENSOR
INSTALLATION AND MAINTENANCE INSTRUCTIONS
32 mm
=
246 g
50-60 mm
BULGE
MARK ON
SENSOR HEAD
BREAK TAB AT DOTTED LINE BY
TWISTING TOWARDS CENTRE OF
BASE
Pittway Tecnologica S.r.l. Via Caboto 19/3, 34147 TRIESTE, Italy
22051E-RF
DESCRIPTION
The 22051E-RF radio sensor is a battery operated RF device designed for
use with the M200G-RF radio gateway. It contains a wireless transceiver
40°C
and runs on an addressable fire system (using a compatible proprietary
communication protocol).
-30°C
It is an optical smoke sensor.
The sensor plugs into the B501RF wireless sensor base.
This device conforms to EN54-25 and EN54-7. It complies with the
requirements of 2014/53/EU for conformance with the RED directive.
SPECIFICATIONS
Supply Voltage:
Standby Current:
Red LED Current Max: 4mA
Re-sync time:
Batteries:
Battery Life:
Radio Frequency:
RF output power:
Range:
Relative Humidity:
INSTALLATION
This equipment and any associated work must be installed in accordance
with all relevant codes and regulations.
Figure 1 details the installation of the B501RF base.
Spacing between radio system devices must be a minimum of 1m
Figure 2 details attaching the sensor head to the base.
Anti-Tamper Features
The base includes a feature that, when activated, prevents removal of the
sensor from the base without the use of a tool. See Figures 3a and 3b for
details on this.
Head Removal Warning - An alert message is signalled to the CIE via the
Gateway when a head is removed from its base.
Figure 4 details the battery installation and the location of the rotary
address switches.
Batteries should only be installed at the time of commissioning
Using these battery products for long periods at temperatures below
-20°C can reduce the battery life considerably (by up to 30% or more)
Observe the battery manufacturer's precautions for use and
Do not mix batteries from different manufacturers
SETTING THE ADDRESS
Set the loop address by turning the two rotary decade switches on the
underside of the sensor (see figure 4), using a screwdriver to rotate the
wheels to the desired address. The device will take one sensor address
on the loop. Select a number between 01 and 159 (Note: The number of
addresses available will be dependent on panel capability, check the panel
documentation for information on this).
PROGRAMMING
To load network parameters into the RF sensor, it is necessary to link the RF
gateway and the RF sensor in a configuration operation. At commissioning
time, with the RF network devices powered on, the RF gateway will
connect and programme them with network information as necessary. The
RF sensor then synchronises with its other associated devices as the RF
mesh network is created by the gateway. (For further information, see the
Radio Programming and Commissioning Manual - ref. D200-306-00.)
NOTE: Do not run more than one interface at a time to commission
devices in an area.
I 56- 4224- 003
3.3 V Direct Current max.
@ 3V: 120 µA (typical in normal operating mode)
35s (max time to normal RF communication from
device power on)
4 X Duracell Ultra123 or Panasonic Industrial 123
4 years @ 25
C
o
865-870 MHz;
14dBm (max)
500m (typ. in free air)
10% to 93% (non-condensing)
Important
Warning
requirements for disposal
E N G L I S H
I56-4224-003

Publicidad

Tabla de contenido
loading

Resumen de contenidos para System Sensor 22051E-RF

  • Página 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS DESCRIPTION 104 mm The 22051E-RF radio sensor is a battery operated RF device designed for use with the M200G-RF radio gateway. It contains a wireless transceiver 40°C and runs on an addressable fire system (using a compatible proprietary...
  • Página 2 TEST MAGNET 10 years. 0333 16 DOP-IRF-021 Figure 6: Cleaning the Sensor System Sensor Europe, Life Safety Distribution GmbH Javastrasse 2, 8604 Hegnau, Switzerland EN54-25: 2008 / AC: 2010 / AC: 2012 Components using radio links SENSOR COVER EN54-7: 2000 / A1: 2002 / A2: 2006 Smoke detectors...
  • Página 3: Specifiche Tecniche

    PER SENSORE RADIO DI FUMO FOTOELETTRONICO DESCRIZIONE 104 mm Il sensore 22051E-RF è un dispositivo a radiofrequenza alimentato a batteria, progettato per essere impiegato con il gateway radio M200G- 40°C RF. Contiene un ricetrasmettitore e viene integrato in un sistema...
  • Página 4 I rivelatori anti-incendio non durano indefinitamente. Se ne consiglia la Figura 6: Pulizia del sensore sostituzione dopo 10 anni. CALOTTA DEL System Sensor Europe Life Safety Distribution GmbH DOP-IRF-021 0333 16 SENSORE Javastrasse 2, 8604 Hegnau, Switzerland...
  • Página 5: Descripción

    INSTRUCCIONES DE INSTALACIÓN Y MANTENIMIENTO DESCRIPCIÓN 104 mm El sensor 22051E-RF es un dispositivo vía radio diseñado para el uso con la pasarela vía radio M200G-RF. Contiene un transceptor vía radio y 40°C funciona en un sistema antiincendios direccionable (utilizando un protocolo...
  • Página 6: Limpieza

    IMÁN DE PRUEBA tener en cuenta el ambiente al seleccionar y colocar sensores de fuego. Los sensores de humo no duran para siempre. Recomendamos sustituirlos cada 10 años. System Sensor Europe Figura 6: Limpieza del sensor Life Safety Distribution GmbH DOP-IRF-021...
  • Página 7: Technische Daten

    D E U T S C H FUNK OPTISCHER RAUCHMELDER INSTALLATIONS- UND WARTUNGSANLEITUNG BESCHREIBUNG 104 mm Der Funkmelder 22051E-RF ist ein batteriebetriebenes HF-Gerät für den Einsatz mit dem Funk-Gateway M200G-RF. Es beinhaltet einen drahtlosen Sender/ 40°C Empfänger und wird über ein adressierbares Brandmeldesystem betrieben. (mit B501RF 32 mm Einsatz eines kompatiblen, proprietären Kommunikationsprotokolls).
  • Página 8 TESTMAGNET Rauchmelder halten nicht ewig. Wir empfehlen einen Austausch nach 10 Jahren. 0333 16 DOP-IRF-021 System Sensor Europe, Life Safety Distribution GmbH Abbildung 6: Reinigung des Melders Javastrasse 2, 8604 Hegnau, Switzerland EN54-25: 2008 / AC: 2010 / AC: 2012...
  • Página 9 62 mm -30°C un protocole de communication propriétaire compatible). Le détecteur se connecte sur le socle sans fil B501 RF. Le 22051E-RF est conforme aux normes NF EN 54-25 et NF EN54-7. Il conforme aussi aux exigences des norme 2014/53/EU (directive RED).
  • Página 10 En utilisant de la fumée ou de la fumée généré d’un aérosol, 0333 16 DOP-IRF021 soumettre le détecteur à une quantité contrôlée de la fumée, System Sensor Europe en respectant les règlementations en vigueur. Le détecteur doit Life Safety Distribution GmbH Javastrasse 2, 8604 Hegnau, Switzerland signaler une alarme feu à...

Tabla de contenido