M08 – LIMIT THRESHOLDS (LIMn, n=1..4)
P08.n.01 Reference measure
P08.n.02 Function
P08.n.03 Upper threshold
P08.n.04 Multiplier
P08.n.05 Delay
P08.n.06 Lower threshold
P08.n.07 Multiplier
P08.n.08 Delay
P08.n.09 Normal status
P08.n.10 Latch
Note: this menu is divided into 4 sections, for limit thresholds LIM1..4
P08.n.01 – Defines which energy meter measurement the limit threshold is applied to.
P08.n.02 – Defines the function of the limit threshold. It can be:
Max = LIMn active when measurement exceeds P08.n.03. P08.n.06 is the reset threshold.
Min = LIMn active when measurement is below P08.n.06. P08.n.03 is the reset threshold.
Min+Max = LIMn active when measurement is above P08.n.03 or below P08.n.06.
P08.n.03 and P08.n.04 – Define the upper threshold, which results from multiplying value P08.n.03 by P08.n.04.
P08.n.05 – Trip delay on upper threshold.
P08.n.06, P08.n.07, P08.n.08 – as above, with reference to the lower threshold.
P08.n.09 – Permits inversion of the status of limit threshold LIMn.
P08.n.10 – Defines whether the threshold is stored and must be reset manually (ON) or is reset automatically (OFF).
M09 – ALARMS (ALAn, n=1..4)
P09.n.01 Alarm source
P09.n.02 Channel number (x)
P09.n.03 Latch
P09.n.04 Priority
P09.n.05 Text
Note: this menu is divided into 4 sections, for alarms L 1..4
P09.n.01 – Signal that causes the alarm. It can be when a threshold (LIMx) is exceeded.
P09.n.02 – Channel number (x), with reference to the previous parameter.
P09.n.03 – Defines whether the alarm is stored and must be reset manually (ON) or is reset automatically (OFF).
P09.n.04 – If the alarm has a priority of high, its activation switches the display to the alarm page automatically and it shows the alarm icon. If instead it is set to low priority, the page does not change and it is
displayed with the 'information' icon.
P09.n.05 – Free text for alarm. 16 characters max.
M11 – ENERGY PULSES (PULn, n=1..2)
P11.n.01 Source measure
P11.n.02 Count unit
P11.n.03 Pulse duration
Note: this menu is divided into 2 sections, for pulses PUL1..2
P11.n.01 – Source measure for pulse generation.
P11.n.02-P11.n.03 – Number of pulses and pulse duration.
M13 – INPUT
P13.01
Input function
P13.02
Rest status
P13.03
ON delay
P13.04
OFF delay
P13.01 – Input function:
OFF – Input disabled
LOCK – Settings lock – prevents access to both levels.
T R- – Energy tariff selection. See tariffing chapter.
C01...C08 – When this input is activated (on the rise time), the corresponding command in the commands menu is carried out.
P13.02 – Input rest status. Permits inversion of the activation logic.
P13.03 – P13.04 – Input activation – deactivation delays. Permits filtering of the status to avoid bounces.
UoM
Default
OFF
OFF- (measures)
Max
Max - Min - Min+Max
0
-9999 - +9999
x1
/100 – x10k
s
0
0.0 – 1000.0
0
-9999 - +9999
x1
/100 – x10k
s
0
0.0 – 1000.0
OFF
OFF
Default
OFF
1
OFF
Low
Low – High
ALAn
(text: 16 characters)
UoM
Default
OFF
pulse/kWh
10
s
0.10
UoM
Default
TAR-A (n=1)
OFF– LOCK –
C01 - C02 - C03 -
C04 - C06 - C07 - C08
OFF
s
0.05
0.00 – 600.00
s
0.05
0.00 – 600.00
Range
G
B
OFF-ON
OFF-ON
Range
OFF-LIMx
1-4
OFF-ON
Range
OFF
Wh+
Wh-
Varh+
Varh-
VAh
100
10
1
0.1
0.01-1.00
Range
TAR-A –
OFF – ON
11

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido