GB
Install profile seal on the DTS cooling unit (side attachment)
WARNING
Danger of accidents due to incorrectly installed seals
Leaky seals can allow moisture to penetrate and cause short-circuits.
 Install the seal so that it provides a tight seal to the switch cabinet.
 Always inspect seals during cleaning and maintenance.
Item
Designation
1
Profile seal
3
Switch cabinet interior fastening
Install profile seals and assemble
Requirements
-
Cut-outs for the DTS cooling unit have been made; see figure
-
The cooling unit is de-energized.
Required tools and material
-
Profile seal (1)
-
Installation tool
-
Accessory kit: Threaded bolts, screws, nuts, washers
Procedure
 Insert profile seals (1) on the sheet metal edge of the cut-outs (2). Fit the seals with the slotted ends (4) down.
 Screw in the two supplied threaded bolts (accessory kit) in the upper fastening points of the DTS cooling unit.
Suspend the cooling unit on the switch cabinet with the threaded bolts installed from outside.
 Tighten the screws for DTS cooling unit on the switch cabinet interior (3). Use the supplied screws, nuts and
washers (accessory kit) to fasten the unit. Firmly tighten the screw fasteners so that the profile seal is pressed
together to a
thickness of 2 mm.
The DTS cooling unit is attached to the switch cabinet and ready for electrical connection;
see
Electrical
connection.
Operating Manual DTS and DTI 6X2E Premium Controller X-Series (XC) 086100099d © Pfannenberg GmbH
1
4
Figure
- Install profile seal
9
DTS cooling unit (side attachment)
2
Item
Designation
2
Cut-touts for seals
4
Profile seal slotted ends
DTS cooling
unit assembly (side attachment).
3
2