GB
6
Troubleshooting
Fault
Unit does not cool;
Evaporator fan
(internal) running
Unit does not cool
sufficiently
Condensate
accumulates in the
switch cabinet
Condensate does not
drain
Condensate drains from
the unit
The blinking of the red LED light on the controller circuit board is not a fault indicator or error message. The red
LED light indicates that voltage is supplied to the cooling unit.
Operating Manual DTS and DTI 6X2E Premium Controller X-Series (XC) 086100099d © Pfannenberg GmbH
Possible causes
• Temperature setting too high.
• Operating limits exceeded.
• Too little coolant.
• Heat exchanger dirty.
• Evaporator fan (internal) defect.
• Condenser fan (external) defect.
• Disturbance in the air circulation
inside the cabinet.
• Exhaust temperature is too high.
• Switch cabinet is not sufficiently
sealed.
• Condensate drain is plugged up.
• Condensate evaporator defector is
too much condensate accumulates.
• Switch cabinet is not sufficiently
sealed.
Corrective measures
Check the temperature setting.
Check the ambient temperature and internal
load.
Call in authorized qualified personnel to
check the unit for leakage.
Clean the heat exchanger.
Call in authorized, qualified personnel;
replace fan.
Check the installation and the path of air
circulating in the switchgear cabinet.
Check the supply and outlet flow of air of
the cooling unit to the inlet and outlet
opening of the switch cabinet.
Close the cabinet door.
Correct leaky points or seals on the switch
cabinet.
Check the temperature setting.
Clean the condensate drain.
Check whether the condensate drain hose
is free from kinks and is installed with a
downward slope.
Correct leaky points or seals on the switch
cabinet.
Page 40 / 42