Product Specifications - Briggs & Stratton 071048 Manual Operario

100/150/200 amperios interruptor de transferencia automatica
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Product Specfications
Model 071048
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................100 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ...............................................................................................2
Frequency ................................................................................60 Hz
Fault Current Rating ..........
22,000 RMS Symmetrical Amperes on Utility Side
.................................
10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ............... -28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................27 kg (59 lbs)
Model 071049
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................200 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ...............................................................................................2
Frequency ................................................................................60 Hz
Fault Current Rating ..........
25,000 RMS Symmetrical Amperes on Utility Side
.................................
10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ............... -28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................28 kg (63 lbs)
This transfer switch is a UL Listed device.
12
Automatic Transfer Switch
Model 071054
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................200 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ...............................................................................................2
Frequency ................................................................................60 Hz
Fault Current Rating ..........
.................................
Normal Operating Range ............... -28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................28 kg (63 lbs)
Model 071070
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................150 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ...............................................................................................2
Frequency ................................................................................60 Hz
Fault Current Rating ..........
.................................
Normal Operating Range ............... -28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................28 kg (63 lbs)
25,000 RMS Symmetrical Amperes on Utility Side
10,000 RMS Symmetrical Amperes on Generator Side
25,000 RMS Symmetrical Amperes on Utility Side
10,000 RMS Symmetrical Amperes on Generator Side
BRIGGSandSTRATTON.COM

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

071054071049071070

Tabla de contenido