Installing recirculation pump
WARNING :
When Hydro Kit is used with the DHW tank, it is STRONGLY recommended to install recirculation pump
to prevent cold water at the end of hot water supply flooding out and to stabilize the water temperature
inside the DHW tank.
- The recirculation pump should be operated when DHW demand is not required. Therefore,
external time scheduler to determine when the recirculation pump should turn on and turn off is
required.
- The operating duration time of the recirculation pump is calculated as follow :
Duration time [minute] = k * V / R
k : 1.2 ~ 1.5 is recommended.
(If distance between pump and tank is far, then choose high number.)
V : Volume of DHW tank [liter]
R : Water flow rate of pump [liter per minute], which is determined by pump performance curve.