9 - Parameter List
Parameter name - ERC 214
Configuration
Main switch
-1=service, 0=OFF, 1=ON
Predefined applications
AP0, AP1, AP2, AP3, AP4, AP5, AP6
Sensor type selection
n5=NTC 5 K, n10=NTC 10 K,
Ptc=PTC, Pt1=Pt1000
DO4 configuration
Lig=light, ALA=alarm
Reference/thermostat
Temperature setpoint
Differential
Min set point limitation
Max set point limitation
Display offset
(correction value in display temperature)
Display Unit (°C/°F)
Calibration of Sair
(offset for air temperature calibration)
Main switch
-1=service, 0=OFF, 1=ON
Night set back
(offset temperature during night mode)
Thermostat reference displacement
(offset temperature)
Pull-down duration
Pull-down limit temperature
Note: hidden parameters are greyed out
DKRCE.PI.RL0.H7.ML
Code
Min
Max
Unit
cFg
r12
-1
1
o61
AP0
AP6
o06
n5
Pt1
o36
Lig
ALA
r--
r00
-100.0
200.0
C/F
r01
0.1
20.0
K
r02
-100.0
200.0
C/F
r03
-100.0
200.0
C/F
r04
-10.0
10.0
K
r05
-C
-F
r09
-20.0
20.0
K
r12
-1
1
r13
-50.0
50.0
K
r40
-50.0
50.0
K
r96
0
960
min
r97
-100.0
200.0
C/F
Installation Guide | ERC 214
App. 0
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
(Def.)
1
1
1
1
AP0
AP1
AP2
AP3
n10
n10
n10
n10
Lig
Lig
Lig
Lig
2.0
4.0
2.0
-24.0
2.0
2.0
2.0
2.0
-35.0
2.0
0.0
-26.0
50.0
6.0
4.0
-20.0
0.0
0.0
0.0
0.0
-C
-C
-C
-C
0.0
0.0
0.0
0.0
1
1
1
1
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0
0
0
0
0.0
0.0
0.0
0.0
1
1
1
AP4
AP5
AP6
n10
n10
n10
Lig
Lig
Lig
2.0
-24.0
2.0
2.0
2.0
2.0
0.0
-26.0
-35.0
4.0
-20.0
50.0
0.0
0.0
0.0
-C
-C
-C
0.0
0.0
-
1
1
-
0.0
0.0
0.0
0.0
0.0
-
0
0
-
0.0
0.0
-
| 15