3 - Quick Configuration at Power Up
y
STEP 1: Power on
y
STEP 2: Select the quick configuration menu
Within 30 seconds of power on, press "<" BACK for 3 seconds.
The main switch "r12" is automatically set to OFF.
y
STEP 3: Select pre-installed application "o61"
The display automatically shows the application selection parameter "o61".
Press SET to select the pre-installed application.
The display shows the default value (eg. "AP0" flashing).
Choose the application type by pressing UP/DOWN and press SET to confirm.
The controller presets parameter values according to the selected application and does not hide relevant parameters.
Tip: you can easily move from AP0 to AP6, and thus select the simplified list of parameters, by pressing the UP key
(circular list).
App
Description
App 0
None (no preset application)
App 1
Medium temperature (2 – 6 °C), ventilated ref. units with timed natural defrost
App 2
Medium temperature (0 – 4 °C), ventilated ref. units with timed electrical defrost
App 3
Low temperature (-26 – -20 °C), ventilated ref. units with timed electrical defrost
App 4
Medium temperature (0 – 4 °C), ventilated ref. units with electrical defrost (by temperature)
App 5
Low temperature (-26 – -20 °C), ventilated ref. units with electrical defrost (by temperature)
App 6
None (no preset application) with simplified parameter list
| 6
Installation Guide | ERC 214
DKRCE.PI.RL0.H7.ML