Wiring Connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminals as identiÀ ed with their
respective matched numbers on the terminal block of indoor and outdoor
unit.
3. When connecting the connecting cable to the outdoor unit terminals, make
a loop as shown in the installation diagram of indoor and outdoor unit to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any water coming in the
outdoor unit. Proceed them so that they do not touch any electrical or metal
parts.
Stripping length of the connecting cable
Terminal
1
2
3
L
N
block
Connecting
Power
cable
cord
Gas Leak Test
Valve cover
Electric parts
cover
Check places for
the outdoor unit.
Remote Control A-B Selection
• When two indoor units are installed in the same room or adjacent two
rooms, if operating a unit, two units may receive the remote control signal
simultaneously and operate. In this case, the operation can be preserved
by setting either one remote control to B setting. (Both are set to A setting
in factory shipment.)
• The remote control signal is not received when the settings of indoor unit
and remote control are different.
• There is no relation between A setting/B setting and A room/B room when
connecting the piping and cables.
To separate using of remote control for each indoor unit in case of 2 air
conditioner are installed near.
Remote Control B Setup.
1. Press RESET button on the indoor unit to turn the air conditioner ON.
2. Point the remote control at the indoor unit.
3. Push and hold
button on the Remote Control by the tip of the pencil.
"00" will be shown on the display.
4. Press
during pushing
disappear and the air conditioner will turn OFF. The Remote Control B is
memorized.
1 2 3
L N
40
30
30
Earth line
Earth line
Connecting cable
Power cord
Check places for
the indoor unit.
• Check the Á are nut
connections for the gas
leak with a gas leak
detector or soap water.
. "B" will show on the display and "00" will
Model
Power source
Maximum running current
Plug socket & fuse rating
Power cord
CAUTION
• Wrong wiring connection may cause some electrical parts burn out.
• Be sure to comply with local cords on running the wire from indoor unit
to outdoor unit (size of wire and wiring method, etc.).
• Every wire must be connected À rmly.
• This installation fuse (15A) must be used for the power supply line of
this air conditioner.
• If incorrect or incomplete wiring is carried out, it will cause an ignition or
smoke.
• Prepare the power supply for exclusive use with the air conditioner.
• This product can be connected to the mains.
Connection to À xed wiring: A switch which disconnects all poles and
40
has a contact separation of at least 3 mm must be incorporated in the
À xed wiring.
NOTE
• Wire type : More than H07RN-F or 245 IEC66 (1.0 mm
OTHERS
OTHERS
Note : 1. Repeat above step to reset Remote Control to be A.
2. Remote Control A has not "A" display.
3. Default setting of Remote Control from factory is A.
To switch to the TEST RUN
(COOL) mode, press RESET
button for 10 seconds.
(The beeper will make a short
beep.)
This product is designed so that, after a power failure, it can restart
automatically in the same operating mode as before the power failure.
Information
The product was shipped with Auto Restart function in the off position.
Turn it on as required.
How to set the Auto Restart
1. Press and hold the RESET button on the indoor unit for 3 seconds to set
the operation (3 beep sound and OPERATION lamp blink 5 time/sec for
5 seconds).
2. Press and hold the RESET button on the indoor unit for 3 seconds to
cancel the operation (3 beep sound but OPERATION lamp does not
blink).
• In case of ON timer or OFF timer are set, AUTO RESTART OPERATION
does not activate.
8
B10, B13, B16N3KVP Series
50Hz, 220 – 240 V Single phase
60Hz, 220 V Single phase
H07RN-F or 245 IEC66 (1.5 mm
: Connecting cable
Test Operation
RESET button
Auto Restart Setting
11A
15A
2
or more)
2
or more).