Refrigerant Piping Connection; Evacuating - Toshiba RAS-B10N3KVP Serie Manual Del Usuario

Ocultar thumbs Ver también para RAS-B10N3KVP Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 11

Refrigerant Piping Connection

Flaring
1. Cut the pipe with a pipe cutter.
90°
2. Insert a Á are nut into the pipe and Á are the pipe.
• Projection margin in Á aring : A (Unit : mm)
Rigid (clutch type)
Outer dia.
R410A tool used
of copper pipe
Ø6.35
Ø9.52
Ø12.70
Imperial (wing nut type)
A
Outer dia. of copper pipe
Die
Pipe
Tightening connection
Align the centers of the connecting pipes and tighten the Á are nut as far as
possible with your À ngers. Then tighten the nut with a spanner and torque
wrench as shown in the À gure.
Half union
Externally
threaded side
Use a wrench to secure.
CAUTION
Do not apply excess torque. Otherwise, the nut may crack depending on
the conditions.
Outer dia. of copper pipe
Ø6.35 mm
Ø9.52 mm
Ø12.70 mm
• Tightening torque of Á are pipe connections
The operating pressure of R410A
is higher than that of R22 (approx.
1.6 times). It is therefore necessary
to À rmly tighten the Á are pipe
connecting sections (which connect
the indoor and outdoor units) up to the
speciÀ ed tightening torque. Incorrect
connections may cause not only a
gas leakage, but also damage to the
refrigeration cycle.
Shaping pipes
1. How to shape the pipes
Shape the pipes along the incused line on
the outdoor unit.
2. How to À t position of the pipes
Put the edges of the pipes to the place with
a distance of 85 mm from the incused line.
Obliquity
Roughness
Warp
Conventional tool
used
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
R410A
Ø6.35
1.5 to 2.0
Ø9.52
1.5 to 2.0
Ø12.70
2.0 to 2.5
Flare nut
Internally
threaded side
Use a torque wrench to tighten.
(Unit : N·m)
Tightening torque
14 to 18 (1.4 to 1.8 kgf·m)
33 to 42 (3.3 to 4.2 kgf·m)
50 to 62 (5.0 to 6.2 kgf·m)
Flare at indoor
unit side
Flare at outdoor
unit side
Incused line

Evacuating

After the piping has been connected to the indoor unit, you can perform the
air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the indoor unit using a
vacuum pump. Do not use the refrigerant in the outdoor unit. For details,
see the manual of the vacuum pump.
Using a vacuum pump
Be sure to use a vacuum pump with counter-Á ow prevention function so that
inside oil of the pump does not Á ow backward into pipes of the air conditioner
when the pump stops.
(If oil inside of the vacuum pump enters the air conditioner, which use R410A,
refrigeration cycle trouble may result.)
1. Connect the charge hose from the manifold valve to the service port of the
packed valve at gas side.
2. Connect the charge hose to the port of the vacuum pump.
3. Open fully the low pressure side handle of the gauge manifold valve.
4. Operate the vacuum pump to start evacuating. Perform evacuating for
about 15 minutes if the piping length is 25 meters. (15 minutes for 25 meters)
(assuming a pump capacity of 27 liters per minute) Then conÀ rm that the
compound pressure gauge reading is –101 kPa (–76 cmHg).
5. Close the low pressure side valve handle of the gauge manifold valve.
6. Open fully the valve stem of the packed valves (both gas and liquid sides).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
Compound pressure gauge
–101 kPa
(–76 cmHg)
Handle Lo
Charge hose
(For R410A only)
Connecting pipe
Packed valve at gas side
Service port (Valve core (Setting pin))
Packed valve at liquid side
CAUTION
• KEEP IMPORTANT 5 POINTS FOR PIPING WORK.
(1) Take away dust and moisture (inside of the connecting pipes).
(2) Tighten the connections (between pipes and unit).
(3) Evacuate the air in the connecting pipes using a VACUUM PUMP.
(4) Check gas leak (connected points).
(5) Be sure to fully open the packed valves before operation.
Packed valve handling precautions
• Open the valve stem all the way out, but do not try to open it beyond the
stopper.
Pipe size of Packed Valve
12.70 mm and smallers
15.88 mm
• Securely tighten the valve cap with torque in the following table.
Cap Size
Cap
(H)
14~18 N·m
H17 - H19
(1.4 to 1.8 kgf·m)
Valve Rod
Cap
33~42 N·m
H22 - H30
(3.3 to 4.2 kgf·m)
8~12 N·m
H14
(0.8 to 1.2 kgf·m)
Service
Port Cap
14~18 N·m
H17
(1.4 to 1.8 kgf·m)
7
Pressure gauge
Manifold valve
Handle Hi
(Keep full closed)
Charge hose
(For R410A only)
Vacuum pump adapter for
counter-Á ow prevention
(For R410A only)
Vacuum
pump
Size of Hexagon wrench
A = 4 mm
A = 5 mm
Torque
Hexagon wrench
is required.
Service Port Cap
Valve Rod Cap
EN
ES
FR
IT
DE
PT
PL
CZ
RU
CR
HU
TR
NL
GR
SV
FI
NO
DK
RO
BG
EE
LV
A
H
SK
SI

Publicidad

Tabla de contenido
loading

Tabla de contenido