5. Electrical connection
Electrical connection must be carried out
by a qualified electrician in accordance
with local regulations.
Follow all safety standards.
The unit must be properly earthed (grounded).
Follow the instructions in the wiring diagram
hereto attached.
Once the electrical connection has been
completed, remove any pieces of wire, sheath,
washers or any other foreign bodies that may be
found inside the electric control panel.
5.1. Capacitor
Fasten the capacitor in the suitable seat
through the supplied clamp and connect it
through the terminals.
6. Starting
When the control unit is turned on, the pump is on
STOP (factory setting).
After making the connections, close the control
unit and turn on the power.
The first line of the display shows the message
PUMP STOPPED and the second line shows
wh xxxx (working hours) and the power line
voltage.
Before
starting
programming parameter menu with
pushbutton, select the dialogue language and then
change the factory settings in the various
parameters (see paragraph 3.1.1.). When the
settings have all been changed, press the
(PROG) pushbutton and exit the programming
page.
The
display
shows
STOPPED, wh (working hours) and the power line
voltage.
To start the pump, press the
pushbutton and the pump switches to automatic
functions.
The top line shows the message PUMP ON
AUTOMATIC and the pump works according to
the signals from the pressure switch or float
switch.
When the pump is working, the top line shows the
PF value and the current intake by the motor; the
bottom line shows the working hours and the
power line voltage.
the
pump,
access
the
message
(AUT-STOP)
7. Operation
The pump can work automatically with the signals
from the pressure switch (pressure circuit) or a
float switch (tank filling).
8. Accessories
8.1. RA 100
Control panel for remote alarm
Dimensions: 110x150x70
Power supply: 220-230 V single-phase
Signals all PFC-M control panel malfunctions
detected.
5-Watt flashing red light plus 75 dB - 3600 Hz
acoustic alarm, for use in areas of loud noise,
positioned in such a way as to be visible from a
distance.
The control panel is fitted to an energized panel
led and an alarm reset pushbutton.
the
(PROG)
8.2. MSP 1M
(Volt Free Contact Module)
A module featuring a free contact (0,1A - 50V), to
be connected to an alarm signal system.
PUMP
Control box without electrical supply or in alarm:
opened contact (cutout signal).
Control box energized, without any alarm: closed
contact (electrical signal continuity).
9. Disposal
Observe the local regulations and dispose of any
control gear accordingly. This product contains
electrical and electronic components and should
be disposed of accordingly.
RA 100
MSP 1M