Use the arrow keys and the number pad to change the Max, Min, and Tare values. Then
select PREVIOUS MENU and press ENTER.
Press START to confirm saving the data or STOP to exit without saving.

CALIBRATING THE OIL SCALE

Access the CALIBRATION MENU as explained above.
The following screen will be displayed:
Select OIL SCALE and press the ENTER key. The following screen will be displayed:
Empty the oil containers. Replace the empty containers in their lodgings, taking care not to
exert pressure on the scale, and press START. The following screen will be displayed:
Fill the new oil container with a known volume of new oil (from 100 a 250 cc measured on the
container measure marks). Replace the container in its lodging, taking care not to exert
pressure on the scale. Use keys 0 through 9 to type in the known oil volume, in cc, and press
START. Select "PREVIOUS MENU" to exit the CALIBRATION MENU. Press START to save
the data. Switch off the machine and disconnect it from the electrical supply.

CALIBRATING THE BOTTLE PRESSURE TRANSDUCER

Remove the rear plastic cover of the machine to access the bottle. Close the blue tap on the
bottle and the tap under the high-pressure filter (3, Fig.11). Slowly unscrew the blue hose from
the bottle to bring the pressure in the bottle transducer to zero bar. Switch the machine on.
Access the CALIBRATION MENU as explained above.
The following screen will be displayed:
INSTRUCTIONS MANUAL
Min
x:xx lb
Tare
x:xx lb
PREVIOUS MENU
SAVE DATA:
press START.
To exit:
press STOP
BOTTLE SCALE
<OIL SCALE>
BOTTLE PRESSURE TR.
A/C PRESSURE TR.
ZERO LEVEL
empty oil containers
levels
xxxxx
press START
REFERENCE VALUE
xxxx cc
levels
xxxx
press START
BOTTLE SCALE
OIL SCALE
<BOTTLE PRESSURE TR.>
A/C PRESSURE TR.
-22-