Configuration
I/O assignment menu
Code
Assignment
- - - - r r r r 2 2 2 2
Relay R2
no : not assigned
FtA : frequency threshold reached. The contact is closed if the motor frequency is greater
than or equal to the threshold set by Ftd (1)
CtA : current threshold reached. The contact is closed if the motor current is greater than
or equal to the threshold set by Ctd (1)
SrA : speed reference reached. The contact is closed if the motor frequency is greater than
or equal to the speed reference
tSA : thermal threshold reached. The contact is closed if the motor thermal state is greater
than or equal to the threshold set by ttd (1)
- - - - A A A A d d d d d d d d Address of the speed controller when it is controlled via the serial link.
Adjustable from 1 to 31.
- - - - b b b b d d d d r r r r Serial link transmission speed :
9.6 = 9600 bits / s or 19.2 = 19200 bits / s
19200 bits / s is the transmission speed for operating the remote display module.
Modification of this parameter is only taken into account after the speed controller has been
powered down then powered up.
(1) Assigning this function displays the corresponding settings in the SEt- menu so that they can be adjusted.
I I I I - - - - 0 0 0 0 - - - -
(continued)
Factory
setting
SrA
1
19.2
82