ERROR MESSAGES
The Syclone LGR control system constantly monitors internal operating conditions. If the system detects a problem, it will
produce an error ("ER") message indicating the problem. If the display shows an ER message, first unplug the unit and
then plug it back in. This will usually reset the electronics, and the unit will begin operating normally. If the error message
reappears, refer to the explanation and solution shown below. If this still does not fix the problem, contact your Aramsco
location for assistance.
NOTE: The message "POWER FAILURE" is not a system error. When this message is displayed, it indicates that
power to unit was interrupted and then restored. To clear the message, press the
C O N T R O L P A N E L
M E S S A G E
ER1 CONTACT SERVICE
CENTER
ER2 CONTACT SERVICE
CENTER
ER3 CONTACT SERVICE
CENTER
ER4 √ DEFROST SENSOR
CONNECT
– alternate message –
ER4 √ OUTLET SENSOR
CONNECT
ER5 √ SENSOR
CONNECTION ON BD
ER6 CONTACT
SERVICE CENTER
ER7 INVALID
MODEL SETTING
ER8 BUTTON STUCK √
ALL BUTTONS
ER9 PUMP BLOCKED √
CHECK PUMP & HOSE
07-01922C F532-120V 2015-03 Warranty 07-01939
E X P L A N A T I O N A N D S O L U T I O N
Voltage error. Confirm that unit is connected to a suitable AC power supply and that the
circuit is not overloaded. If supply is correct, the electronic control panel may require
replacement. If error persists, contact service.
Control panel error. The electronic control panel may require replacement. If error
persists, contact service.
Unit in defrost too long. Check defrost sensor cable for proper connection. See
"Inspecting the Control Panel," p. 17, for instructions. If error persists, sensor assembly
may require replacement. Contact service.
Sensor error. Check defrost sensor cable for proper connection. See "Inspecting the
Control Panel," p. 17, for instructions. If error persists, sensor assembly may require
replacement. Contact service.
Low voltage board error. Check outlet temp sensor cable for proper connection. See
"Inspecting the Control Panel," p. 17, for instructions. If error persists, sensor assembly
may require replacement. Contact service.
High voltage error. The high voltage board may require replacement. If error persists,
contact service.
Control board DIP switch settings or firmware version may be incorrect. If error persists,
contact service. Service may ask you to verify DIP switch settings. See "Inspecting the
Control Panel," p. 17, for instructions.
Press each membrane key and check for proper operation. If a key doesn't function, or
if the error persists, the membrane overlay may require replacement. Contact service.
Check for obstructions in drain hose. If clogged, remove hose from unit and blow tube
out with compressed air. Inspect and clean the pump check valve and pump basin. See
"Cleaning and Servicing the Check Valve Pump," p. 11.
19
MENU SELECTION key.
Aramsco