Night Mode - Calpeda I-MAT Serie Instrucciones De Uso

Ocultar thumbs Ver también para I-MAT Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 90
Par.
Description
AP02
Primary transducer supply
Primary transducer
AP03
measuring unit
Primary transducer
AP04
EN
minimum value
Primary transducer
AP05
maximum value
Secondary transducer
AP06
supply
Secondary transducer
AP07
measuring unit
Secondary transducer
AP08
minimum value
Secondary transducer
AP09
maximum value
Secondary transducer
AP10
mode
UP02
Nominal pump current
UP03
Nominal pump frequency
UP05
Operating mode
UP06
Primary set-point
tC01
System type
9.4.3. Automatic
frequency.
In this operating mode typically the pump runs
continuously without stop. If it is required to stop the
pump when it's working at the minimum operating
frequency (parameter SA03) it's necessary to
change the value of the parameter AP16 from "Off"
to "FM".
The system will restart when the temperature of the
system will reach the value of parameter tC02.
9.5. Constant flow operating mode.
Constant flow rate mode keeps constant the flow in
a point of the system.
This configuration uses a feedback given by a flow
sensor (connected as shown in section 6.7).
Parameters to programm or check (recommended
sequence):
Par.
Description
AP02
Primary transducer supply
Primary transducer
AP03
measuring unit
Primary transducer
AP04
minimum value
Primary transducer
AP05
maximum value
UP02
Nominal pump current
UP03
Nominal pump frequency
UP05
Operating mode
UP06
Set-point
Page 34 / 144
Suggested value
data sheet
transducer
4 [°C]
data sheet
transducer
data sheet
transducer
data sheet
transducer
4 [°C]
data sheet
transducer
data sheet
transducer
DiFF
see motor plate
see motor plate
tC
on demand [°C]
HEAt/Cool
pump
stop
at
minimum
Suggested value
data sheet
transducer
2 [mc/h]
data sheet
transducer
data sheet
transducer
see motor plate
see motor plate
CF
on demand [mc/h]
9.6. Fixed speed operating mode.
In this mode the system works as a traditional
pump with fixed curve.
9.6.1. Fixed speed operating mode controlled
by keyboard.
Parameters to programm or check (recommended
sequence):
Par.
Description
UP02
Nominal pump current
UP03
Nominal pump frequency
UP05
Operating mode
Man1
Primary fixed speed
operating frequency
To allow which the system works properly,
the operating frequency is limited between
parameter
SA03
frequency) and parameter UP03 (nominal
frequency of the pump).
9.6.2. Fixed speed operation by an external
reference.
If it is necessary to control the frequency from an
external unit it is required to make the connection
as described in section 6.8.
Parameters to programm or check (recommended
sequence):
Par.
Description
UP02
Nominal pump current
UP03
Nominal pump frequency
UP05
Operating mode
AP02
Primary transducer supply
Primary transducer minimum
AP04
value
Primary transducer maximum
AP05
value
Man3
Remote control activation
Minimum value for remote
Man4
control
The maximum frequency (parameter UP03) will
be related to the maximum value of the external
reference.

9.7. Night mode

Night mode is an optional operating mode which
reduces the frequency of the system when the
temperature is below a certain value.
This option use a feedback of a temperature
transducer connected as described in section 6.7.
(secondary transducer electrical connection).
Because on I-MAT only two analog inputs
are available, this option does not allow
other options or operating modes which
need 2 transducers (i.e. differential mode).
Parameters to programm or check (recommended
sequence):
I-MAT_Ed5 - Operating Instructions
Suggested value
see motor plate
see motor plate
Man
on demand [Hz]
(minimum
operating
Suggested value
see motor plate
see motor plate
Man
on demand
0
100
On
on demand [Hz]

Publicidad