Maintenance And Care - STEINEL RS Pro 5100 SC Manual

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 47
DC operation
During DC operation, the light output is set to 100%.
Start-up/interruption to power
If the connection to the mains voltage is interrupted,
the settings and current operating status of the light
will be saved and restored once the power supply is
re-established.
Reach adjustment
The reach setting can be infinitely varied between
1 and 10 m. Reach can be reduced in four directions
by fitting the slot-in shrouds included.
• Open twist lock (Fig. 6.1)
• Pull end cap out by approx. 7 cm. Screwed cable
gland need not be undone. (Fig. 6.2)
• Fit slot-in shrouds (Fig. 6.3)
• Push end cap back and close twist lock (Fig. 6.4)
Reach setting examples (Fig. 6.5)
This function for the C models is only applicable in
combination with a Bluetooth-capable device.
Time setting
The light's ON time can be set to any period from
5 seconds to 60 minutes. Any movement detected
before this time elapses will restart the timer.
This function for the C models is only applicable in
combination with a Bluetooth-capable device.
Basic light level
The brightness of the basic light level setting can be
varied between 10% and 50%.
The period for which the basic light level remain ON
can be infinitely varied between 10 minutes and
30 minutes, or set to remain ON all night.
Main light level
The brightness of the main light level setting can be
varied between 50% and 100%.
Twilight setting
The chosen response threshold can be infinitely varied
from 2 to 2000 lux.
This function for the C models is only applicable in
combination with a Bluetooth-capable device.
Grouping
The RS PRO 5100/5150 SC / RS PRO 5100/5150 SC
EM / RS PRO 5100/5150 C can be operated as a
separate luminaire or several luminaires can be inter-
connected in groups via wireless communication.
In each group, a group master must be defined in the
Steinel Connect App. All luminaires in a group operate
in the same way as the group master is configured.
Reach can be set individually for all luminaires in the
lighting group.
Cyclical battery checks limit the suitability of the
RS PRO 5100/5150 SC EM as group master.
The sensor is deactivated during the self-testing
phases. This means that the luminaire is unable to
detect movement during this period.
This function for the C models is only applicable in
combination with a Bluetooth-capable device.
Fade Time
Fade Time can be used to set the rate of dimming
when switching the light ON and OFF (1 s - 3 s).
Neighbouring-light function
The neighbouring-light function can be activated and
deactivated via the Steinel Connect App. This function
assigns the neighbouring groups to the active lighting
group. The active group responds to activation signals
from the neighbouring group assigned to it and switches
to main light or basic light as defined in the settings.
Emergency light (EM)
The "Emergency light (EM) status indicator" is provided
in the form of a two-colour status LED at the sensor-
switched luminaire.
– Status LED intermittent green:
Rechargeable battery regeneration
– Status LED permanently green:
No malfunction / normal state
– Status LED permanently flashing red:
Rechargeable battery faulty / battery charge too low
– Status LED intermittently flashing red:
Light not connected or faulty
– Status LED dark:
Mains power or emergency light control gear faulty

7. Maintenance and care

Maintenance
For maintenance and inspection, follow the regulations
and standards applicable to the emergency light at the
place of installation. Emergency lights and emer-
gency-light control gear must be checked at regular
intervals.
Startup
Started up by: ______________________
Startup date: ______________________
Self-tests "(EM)"
– The self-tests for the sensor-switched luminaire,
status LEDs and rechargeable batteries are per-
formed automatically about every 8 days.
– Self-testing battery capacity by simulating a mains
power failure is done four times a year.
The sensor-switched luminaire continues to provide main
light illumination and sensor detection during the test.
– 17 –
GB

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Rs pro 5150 scRs pro 5100 sc emRs pro 5150 sc emRs pro 5100 cRs pro 5150 c

Tabla de contenido