Descargar Imprimir esta página

Bosch FLM-420-I2-D Guia De Instalacion página 10

Ocultar thumbs Ver también para FLM-420-I2-D:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 11
10
en |
F
i
NOTICE! Installation must only be performed by authorized and specialized personnel!
WARNING! Live components and stripped cable! Risk of injury from electric shock. The
!
system must be current-free during connection work.
CAUTION! Electrostatic discharge (ESD)! Electronic components could become damaged.
Ground yourself using a wrist strap or take other suitable actions.
Functional description
FLM-420-I2 Input interface modules provide three monitoring functions:
1.
Monitoring a line with EOL resistor for standby or triggering (interruption/short circuit)
2.
Monitoring a potential free contact for "open" and "closed" states
3.
Voltage monitoring between 0 and 30 V DC.
The FLM-420-I2-D is installed on a DIN rail in accordance with EN 500022 with enclosed adapter (see Figure 1,
page 3; Removal, see Figure 2, page 4).
Address setting
Fit a rotary switch in the required position using a pan head slotted screwdriver (see Figure 3, page 5).
It is not permitted to use different operating modes in the same loop/stub/T branch next to each other!
Address (A)
Operating mode
0 0 0
Loop/stub in LSN improved version mode with automatic addressing
0 0 1 ... 2 5 4
Loop/stub/T branches in LSN improved version mode with manual addressing
CL 0 0
Loop/stub in LSN classic mode (address range: max. 127)
2 5 5 ... 2 9 9
Non-permitted address range (error message on fire panel)!
Connection (see Figure 4, page 6)
Description
LSN: b1+ | a- | b2+
IN: IN1+ | IN1- | IN2+ | IN2-
Technical specifications
Inputs
LSN input voltage
Max. current consumption from LSN
Contact monitoring:
EOL resistor
Max. current strength (current pulse)
Total resistance of the line
Voltage monitoring:
Voltage range
Input resistance
Number of selectable thresholds
Permissible wire diameter
Cable length per input
Permissible operating temperature
Permissible storage temperature
Permissible rel. humidity
Protection class as per IEC 60529
Safety class as per IEC 60950
EMC interference immunity
EMC emitted interference
Housing material and color
Dimensions (with adapter)
F.01U.012.988 | A4 | 2008.06
FLM-420-I2-W Input interface module type DIN rail | Installation manual
Function
LSN b incoming | LSN a | LSN b outgoing
Input 1 | Input 2
2, independent
15 to 33 V DC (min. to max.)
10.4 mA
Nominal, 3.9 kΩ
8 mA
0 to 30 V DC
> 50 kΩ
4 (see programming software)
0.6 to 3.3 mm
max. 3 m
-20 °C ... +65 °C
-25 °C ... +80 °C
<96%, non-condensing
IP 30
III
EN 54-18, EN 50130, VDS 2540
EN 61000-6-3
PPO (Noryl), gray white (similar to RAL 9002)
approx. 110 mm x 110 mm x 48 mm (W x H x D)
In standby: 1500 Ω to 6000 Ω
Short-circuit: < 800 Ω
Interruption: > 12000 Ω
2
Bosch Sicherheitssysteme GmbH

Publicidad

loading