Open connection area
↻ Component is securely installed on the inverter.
1 Set the DC switch to the "OFF" position.
2 Unfasten the cover with lever via the 4 screws [
3 Remove cover and place back in the packaging.
4.2
Making the electrical connections
NOTE
Select conductor cross-section, safety type and safety value in accordance with the following basic condi-
tions:
Country-specific installation standards; power rating of the device; cable length; type of cable installation;
local temperature
Detailed information on tightening torques: See comprehensive operating instructions under
ergy.com/de/downloads
4.3
Configuring the DC cable
↻ DC cables inserted through the input plate.
↻ CAUTION! Risk of fire due to chemical corrosion. Cable lugs must be suitable
for the conductor material and copper busbars being used .
↻ WARNING! Risk of short circuit due to incorrect size of the cable lug! Observe
the dimensions for the selection. [See figure 4] [} Page 5]
1 Fit the DC cables with a ring cable lug. When crimping, ensure that the ring ca-
ble lug is rotated in accordance with the final installation position. [See figure
5] [} Page 6]
WARNING! Danger to life due to a surge in voltage. If the clearance is insuffi-
cient, shrink tubing (>= 6 kV/mm dielectric strength) must be used.
F Guide the shrink tubing over the uninsulated crimping point and a maximum of
+0/-0.08
0,79
inch over the cable insulation and shrink-fit using manual shrink-fit-
ting equipment.
F Draw in cables to the indicated fixing length and run with cable fitting.
ð DC cable configured. Continue with the connection to DC switch.
4.4
Connecting the DC cable to the component
DC-Breaker
T_25]
4
3
Fig. 3: Open connection area
1
Housing
2
DC switch
3
Cover with lever
4
Screws
http://www.kaco-newen-
Ø 11 mm
max.
1.65
inch
3
2
1
Fig. 4: Configuring the DC cable
1
Cable lug
2
Shrink tubing*
3
DC cable
1
2
Page 79