1
Intended use
This instrument is an advanced combustible gas leak detector, capable of locating many com-
bustible, non combustible and toxic gases.
A partial list of these gases include:
Aceton
Alcohol
Ammonia
Benzene
Butane
Ethylene
Gasoline - Petrol
Hydrogen
The detector is factory calibrated for methane in air.
2
Technical Data
Power Supply: ................................... 1 x 9V battery (alkaline preferred)
Sensor: .............................................. Solid state semi conductor
Sensitivity: ......................................... <50ppm methane
Indicators:.......................................... Audible: Adjustable tic rate
.......................................................... Visual: Flashing LED
Warm-up: .......................................... 10 seconds
Response Time: ................................ Instantaneous
Duty Cycle: ........................................ Continuous
Battery Life: ....................................... 5 hours typical use
Dimensions (HxWxD): ....................... 8"x 4" x 1.5", 205mm x 100mm x 36mm
Weight: .............................................. 15 oz / 460 gm
Probe Length: .................................... 18 inches / 460 mm
Operative:.......................................... 0-50oC / +32-122oF
Protection against Electric Shock
(in accordance with EN 61010-1)
This instrument is designated as Class III, SELV.
Please note: In this equipment the used batteries are to be disposed in accordance with the cur-
rent laws and local guidelines
Industrial Solvents
Jet Fuel
Lacquer Thinners
Methane
Naphtha
Natural gas
Propane
Toluene
.
ENGLISH