EAS ELECTRIC EINSOLAR15Y Manual De Usuario E Instalacion página 22

Ocultar thumbs Ver también para EINSOLAR15Y:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5.3 DC Wire Assembly and Connection
1.
PV modules of the connected strings must be of: the same time, identical
alignment and tilting angle.
2.
Before commissioning and connecting the PV arrays, the DC switch MUST
be open.
3.
Parallel strings must have the same number of modules.
4.
It is mandatory to use the DC connectors within package for the
connection of PV arrays.
5.
The polarity of the PV arrays MUST be compatible to the DC connectors of
the inverter.
6.
The DC input voltage AND DC input current of the PV array MUST never
exceed the maximum input allowance of the inverter.
DC Commissioning
5.4 Residual Current Protection
This product is equipped with residual current protection device internally, in
accordance with IEC 60364-7-712. An external residual current protection
device is not needed.
If the local regulation demands otherwise, it is recommended to install a
30mA Type B residual current protection device.
12
6. COMMUNICATION
6.1 System monitoring via Datalogger - RS485/Wi-Fi /GPRS (Optional)
6.1.1 Wi-Fi /GPRS Datalogger Installation
Unpack the Datalogger from package.
1.
Unscrew the cap in COM1 port.
2.
Plug the Datalogger in and tighten.
For user guidance and configuration of Datalogger, please refer
to the corresponding Wi-Fi Stick Guide manual, which is
available in printed form inside Documents pack, or an online
manual on our website at www.easelectric.es.
6.1.2 Smart Meter/DRED Connection
V.2
13
V.2

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Einsolar25y

Tabla de contenido