Information on grounding components:
Object
Description
1
Housing
2
Terminal lug with protective conductor
3
M6×12 pan head screw
PE Conductor cross-section: 16mm²
5. COMMISSIONING

5.1 Safety Instructions

1.
Measure the frequency and voltage of grid connection and make sure
they follow the inverter's grid connection specifications.
2.
An external circuit-breaker on the AC side (or a fuse) at 1.25*AC rated
current is strongly recommended.
3.
Reliability of all earth connections must be tested and valid.
4.
Before commissioning, disconnect the inverter and the circuit-breaker
or fuse, and prevent accidental reconnection.
10
5.2 AC Wire Assembly and Connection
5.2.1
AC Commissioning
5.2.2 AC Switch Types
Please install an individual 2-stage miniature circuit breaker according
to the following specifications.
Model
EINSOLAR15Y
EINSOLAR25Y
V.2
Maximum output
AC Breaker Rated
current (A)
current(A)
24
32
36.3
50