EAS ELECTRIC EINSOLAR15Y Manual De Usuario E Instalacion página 29

Ocultar thumbs Ver también para EINSOLAR15Y:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

DC
component of
the current
the electricity
exceeds 1A in static
12
state and 4A in
exceeds the
dynamic state
permissible
range
EEPROM
Micro CPU read
Error, e.g.
13
EEPROM failed
transition
disturbance
Master CPU
Internal
communicate
communica-
14
with slave CPU
tion fault
abnormal
Bus-voltage
Bus-voltage is
15
too high
greater than 1000V
Bus-voltage is 20V
lower than
Bus-voltage
standard bus
16
too low
voltage
DRM switch S9
17
DRM S9 Error
fault
3. If it cannot be recovered for a long time,
please confirm:
· whether the AC circuit breaker is disconnected
· whether the AC terminal is in good connection
· whether the power supply line is normal
· whether the safety regulation settings are
normal
Disconnect the inverter from the utility
grid and the PV array, and reconnect it
after LED turns off. If this fault is still being
displayed, please contact the service.
Disconnect the inverter from the
utility grid and the PV array, and
reconnect it after LED turns off. If this fault
is still being displayed, please contact the
service.
Disconnect the inverter from the utility
grid and the PV array, and reconnect it
after LED turns off. If this fault is still being
displayed, please contact the service.
Check the open-circuit voltages of the
strings and make sure it is below the
maximum DC input voltage of the
inverter. If the input voltage lies within the
permissible range while the fault occurs,
please contact the service.
Check the open circuit voltage of the
strings and make sure it is below the
maximum DC input voltage of the inverter.
If the input voltage lies within the
permissible range while the fault occurs,
please contact the service.
Check the connection of DRM device. If
the DRM device is connected normally
while this fault occurs, please contact
the service.
26
18
DRM S0 Error
N and PE
voltage
exceeds
19
permitted
range
V.2
Check the connection of DRM device. If
the DRM device is connected normally
DRM switch S0 fault
while this fault occurs, please contact
the service.
Check if the inverter is securely
grounded.
27
V.2